50
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
PSB-120 Series (2 Phase)
Specifications
Features:
• Multiple overload/ short circuit protection modes
• Efficiency above 91%
• Small size
• DIN rail mountable
• Cooling by free air convection
• UL508 (industrial control equipment) approved
• EN60950-1
• Built-in DC OK relay contact
• 3 year warranty
Cat. No. PSB-12024
DC VOLTAGE 24 V
RATED CURRENT 5A
CURRENT RANGE 0 - 5 A
RATED POWER 120 W
RIPPLE & NOISE (max) 100 mVp-p
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1µF & 47µF parallel capacitor.
VOLTAGE ADJ. RANGE 22 V ~ 27 V
VOLTAGE TOLERANCE -0.03
Tolerance: includes set up tolerance, line regulation and load regulation.
START UP WITH STRONG LOAD ≤ 50,000 µF
CURRENT SHORT CIRCUIT Icc 12A
Max 2 sec.: Hiccup mode
Permanent: Continuous mode
DISSIPATION POWER LOAD mas 11 W
LINE REGULATION ± 0.5%
LOAD REGULATION ± 1%
SETUP, RISE TIME 1 sec. (max)
Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
HOLD UP TIME (Typ.) Typ. 20 msec
VOLTAGE RANGE 187 ~ 264 V AC / 330 ~ 550V AC by switch
FREQUENCY RANGE 47 ~ 63 Hz +-6%
EFFICIENCY (Typ.) >91 %
AC CURRENT (115 – 230 Vac.) 1.0 ~ 0.58 ~ 0.46A
INRUSH CURRENT (Typ.) < 11 A < 5 msec
INTERNAL FUSE T 4 A
EXTERNAL FUSE (recommended) 10 A (MCB curve B)
LEAKAGE CURRENT < 1.5 mA @ 230 Vac
OVERLOAD In (60°C) x 1.5 ³ 3 min.;
Current max. Overload @ 4Vdc (permanent) Imax=In (60°C) x (1.8 ~ 2.2)
OVER VOLTAGE 30 – 35 Vdc
OVER TEMPERATURE Yes. Shuts down output and automatically restarts when the temperature inside goes down
SHORT CIRCUIT PROTECTION 1 Hiccup Mode / 2 Fold Back / 3 Restart After Main - Selectable
DC OK AKTIV SIGNAL (max.) 20 ~ 30 Vdc
WORKING TEMP. -25 up to +70 °C (>60°derating 2.5% °C)
HUMIDITY 95 % at 25°C, no condensation
STORAGE TEMP -40 up to +85 °C
TEMP. COEFFICIENT ± 0.03% / C° (0 – 60 °C)
VIBRATION In according to IEC60068-2-6
SAFETY STANDARDS UL508 approved, IEC/EN 60950, EN 50178, IEC/EN 60950, EN60950-1, PELV EN 60204-1
WITHSTAND VOLTAGE I/P-O/P: 3k VAC I/P-FG: 1.6k VAC O/P-FG: 500 VAC
PROTECTION CLASS IP 20 (EN/IEC 60529)
ISOLATION RESISTANCE 100 MΩ (min) @ 500 Vdc
EMI CONDUCTION & RADIATION EN61000-6-4
HARMONIC CURRENT EN61000-3-2
EMS IMMUNITY EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,
EN 61000-4-6, EN61000-6-2,
The power supply is considered a component which will be installed into a final equipment. The final equipment must be
re-confirmed that it still meets EMC directives.
MTBF IEC 61709 > 500.000 h
POLLUTION DEGREE 2
CONNECTION TERMINAL BLOCK 2.5 mm Screw (24 ~ 14 AWG)
DIMENSION 55x110x105 mm ( 2.16x4.33x4.13 in )
PACKING 0.50 kg ( 1.1 lbs) each
NOTE All parameters NOT specially mentioned are measured at 230V AC input, rated load and 25˚C of ambient temperature.