Power Supply, Primary Switch Mode, Narrow Design MINI-PS-100-240AC/24DC/1 MINI POWER provides: * Extra narrow widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.) * Global use due to a wide range input * A high level of operational safety in complex global networks * Reliable startup of heavy loads due to POWER BOOST The reliability of a power supply determines the availability of individual components in a system and whether complex systems can function safely. The globalization of markets increases the demands placed on the power supply. A wide range input and a high level of availability are required. These requirements are met by MINI POWER. 1. Short Description MINI POWER is the extra narrow power supply, which is available in widths of 22.5, 45, and 67.5 mm (0.886, 1.772, and 2.657 in.). In addition to a 24 V version with output currents of 1 A, 2 A, and 4 A, special voltages are also available with 5 V/3 A, +/-15 V/1 A, and 10 - 15 V/2 A. Reliable startup of heavy loads is ensured by a power reserve of up to 100% - the POWER BOOST. The high level of operational safety is also ensured in complex global networks. MINI POWER also operates in applications where static voltage dips, transient power supply failures or phase failure are common. Large capacitors ensure mains buffering of more than 20 ms at full load. 2. Area of Application MINI POWER can be used globally due to the consistent provision of a wide range input. In this way, your entire system can be tested at any production location in the world and can be delivered to any location in the world without faulty switching of the input voltage. This reduces storage costs and logistical effort. An international approval package including UL 60950 for IT equipment and UL 508 for industrial control equipment enables the device to be used globally. Headquarters: (c) Phoenix Contact GmbH & Co. KG * Flachsmarktstrae 8 * 32825 Blomberg * Germany Phone +49 - 52 35 - 30 0 * Fax +49 - 52 35 - 34 12 00 * www.phoenixcontact.com Local Contact: www.phoenixcontact.com/salesnetwork Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 3. Technical Data 114.5 mm (4.508 in.) L (+) NC NC 99 mm (3.989 in.) DC OK N (-) 22.5 mm (0.886 in.) MINI-PS-100-240AC/24DC/1 1 AC 7 solid 2] flexible AWG [mm Input Output Signal 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 NEC Class 2 Uu torque [Nm] [Ib in.] 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3 0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3 Description Type Order No. Power Supply Primary switch mode, narrow design MINI-PS-100-240AC/24DC/1 29 38 84 0 Technical Data Input Data 1 Nominal input voltage Input voltage range (current consumption) Frequency Current consumption (for nominal values) Inrush current limiting/I2t (+25C [+77F]) Mains buffering for a nominal load (typical) Switch-on time after applying the mains voltage Transient surge voltage protection Input fuse, internal Recommended fuse 100 - 240 V AC (wide range input) 85 - 264 V AC 90 - 350 V DC 45 - 65 Hz 0 Hz 0.5 A (120 V AC)/0.3 A (230 V AC), approximately < 15 A/< 0.6 A2s, typical > 20 ms (120 V AC)/> 110 ms (230 V AC) < 0.2 s Varistor T1.25 AL 250 V (device protection) Line protection switch 6 A, 10 A, Characteristic B (EN 60 898) Output Data 2 Nominal output voltage UN/tolerance Setting range for the output voltage Output current during convection cooling and nominal values POWER BOOST IBOOST (t = 2 min., typical) Nominal output current IN -25C to +60C (-13F to +140F) -25C to +40C (-13F to +104F) Derating Short-circuit current limit Startup of capacitive loads System deviation on: Load change static 10 - 90% Load change dynamic 10 - 90% Input voltage change 10% Maximum power loss No load/nominal load Level of efficiency (typical) Response time UOUT (10% - 90%) Residual ripple/switching peaks (20 MHz) Can be connected in parallel Internal surge voltage protection Resistance to return supply 1.3 A (UOUT = 24 V) 1 A (UOUT = 24 V) 1.3 A (UOUT = 24 V) From +60C (+140F), 2.5% per Kelvin 1.7 A, approximately Unlimited < 1%, typical < 3%, typical < 0.1%, typical 0.9 W/4.5 W > 80% (for 230 V AC and nominal values) < 1.2 ms, typical < 100 mVpp (for nominal values) To increase redundancy and power Yes, limited to 35 V DC, approximately 35 V DC Signal Output Data DC OK (active) (Uout > 0.9 x UN = high signal) LED (Uout > 21.5 V DC = LED permanently on) +24 V signal/20 mA, maximum Green LED 24 V DC/1% 22.5 - 28.5 V DC PHOENIX CONTACT page 2 of 8 Pcs. Pkt. 1 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 General Data Insulation voltage: Input/output Approval package Electrical equipment of machines Safety transformers for switched-mode power supply units Electrical safety (of IT equipment) Industrial control equipment Limitation of output power Equipping high voltage installations with electronic equipment Safety extra-low voltage Safe isolation Protection against dangerous shock currents, basic requirements for safe isolation in electrical equipment Limitation of harmonic line currents EN 60 204 (Surge Voltage Category III) EN 61 558-2-17 EN 60950/VDE 0805 UL/C-UL Recognized UL 60 950 u 1) UL/C-UL Listed UL 508 U 1) LISTED NEC Class 2 EN 50 178/VDE 0160 PELV (EN 60 204) SELV (EN 60 950) VDE 0100-410 DIN VDE 0106-101 According to EN 61000-3-2 Mounting position Can be mounted with spacing - Vertical - Horizontal Degree of protection Class of protection MTBF Housing version Weight Dimensions (W x H x D) Climatic Data Ambient temperature Operation Storage Humidity Vibration Shock Degree of pollution Climatic category 3 kV AC (type test)/3 kV AC (routine test) according to IEC 68-2-6 according to IEC 68-2-27 c On horizontal NS 35 DIN rail according to EN 50022 5 cm (1.969 in.) 0 cm IP 20 , (in closed control cabinets) > 500 000 h according to IEC 1709 (SN 29 500) Polyamide PA, color green 0.21 kg, approximately 22.5 x 99 x 114.5 mm (0.886 x 3.898 x 4.508 in.) -25C to +70C (-13F to +158F) (> +60C [+140F] derating) -40C to +85C (-40F to +185F) Up to 95% at +25C (+77F), no condensation < 15 Hz, amplitude 2.5 mm/15 Hz - 150 Hz, 2.3 g 30 g all space directions 2 (according to EN 50 178) 3K3 (according to EN 60 721) 1) UL approval for ambient tempertatunre up to +60 C (+140 F) Conforms to the EMC Directive 89/336/EEC and the Low Voltage Directive 73/23/EEC EMC (Electromagnetic Compatibility) Noise Immunity According to EN 61000-6-2: 3) Electrostatic discharge (ESD) EN 61000-4-2 Housing Contact discharge: Air discharge: Electromagnetic HF field EN 61000-4-32) Fast transients (burst) EN 61000-4-43) Input: Output: Signal: Surge current loads EN 61000-4-53) Input: Housing Frequency: Field strength: Output: Conducted interference EN 61000-4-62) Voltage dips EN 61000-4-113) Simulation of radiophone EN 50204 I/O/S: Frequency: U0: Input: Frequency: Field strength: Requirements EN 61 000-6-2 MINI-PS-100-240AC/24DC/1 4 kV 8 kV > Level 3 8 kV 8 kV 80 - 1000 MHz 10 V/m Level 3 80 - 1000 MHz 10 V/m 2 kV 2 kV 1 kV asymmetrical5) asymmetrical5) asymmetrical5) 4 kV (Level 4) 2 kV (Level 3) 1 kV (Level 2) 2 kV 1 kV 0.5 kV 0.5 kV 1 kV asymmetrical5) symmetrical4) asymmetrical5) symmetrical4) asymmetrical5) 4 kV (Level 4) 2 kV (Level 4) 0.5 kV (Level 1) 0.5 kV (Level 1) 0.5 kV (Level 1) asymmetrical5) Level 3 0.15 - 80 MHz 10 V 0.15 - 80 MHz 10 V 30% reduction of the input voltage for 0.5 periods See input data: Mains buffering > 20 ms Not required 900 MHz/1800 MHz 20 V/m Noise Emission According to EN 50081-2: Radio interference EN 55011 Class A6) EN 55011 (EN 55022) Class B7) Radio interference EN 55011 Class A6) EN 55011 (EN 55022) Class B7) EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22 EN 61000 corresponds to IEC 1000 2) Criterion A: Normal operating characteristics within the specified limits. 3) Criterion B: Temporary adverse effects on the operating characteristics that the device corrects independently. 4) symmetrical: 5) Cable to cable asymmetrical: Cable to ground 6) Class 7) A: Class B: Industrial application Industrial and domestic applications PHOENIX CONTACT page 3 of 8 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 4. Device View, Connections, and Control Elements 2 4 - 5 - - TD U O - + V + 24 1 A 3 22 MI C D K O + C ER OW P NI 5 8. -2 DC .5 V C D K O V ) 0 (24 N 0- C 10 N C A NC IN +) ( L 1 L NC N 8 -25 - 25 ... + 60 C - 13 ... + 140 F INFORMATION TECHNOLOGY EQUIPMENT u Read installation instructions before connecting to mains INDUSTRIAL CONTROL EQUIPMENT 1YD8 www.interface.phoenixcontact.com TEMPERATURE LISTED U APPROVALS Order No.: 29 38 84 0 7 MINI-PS-100-240AC/24DC/1 6 Power Supply OUTPUT 100-240V 24V DC 50-60Hz 1% Range: 1A 85-264V 0.4-0.2A DC: 90-350V 0.4-0.2A 5 INPUT AC: NC 6 Figure 04 1 AC input: Input voltage 85 - 264 V AC Frequency 45 - 65 Hz (0.2 mm2 to 2.5 mm2 solid) (0.2 mm2 to 2.5 mm2 flexible) (25 - 14 AWG) Internal fuse T1.25 AL 250 V Recommended fuse 6 A or 10 A LS/Characteristic B 2 DC output: Output voltage 24 V DC (default), can be set from 22.5 - 28.5 V DC using a potentiometer4 (0.2 mm2 to 2.5 mm2 solid) (0.2 mm2 to 2.5 mm2 flexible) (25 - 14 AWG) The device is idling-proof and short-circuit-proof. 3 DC OK output active 4 Potentiometer 22.5 - 28.5 V DC 5 DC OK LED 6 Universal latching foot for EN DIN rails 5. Safety and Warning Instructions Installation and startup must only be carried out by qualified personnel. The relevant country-specific regulations (e.g., VDE, DIN) must also be observed. Before startup it is particularly important to ensure that: * The mains have been connected correctly and protection is provided against electric shock. * The device can be switched off outside the power supply according to EN 60950 regulations (e.g., by the line protection on the primary side). * All supply lines have sufficient fuse protection and are the correct size. * All output cables are the correct size for the maximum device output current or have separate fuse protection. * Sufficient convection is ensured. MINI POWER is a built-in device. After installation the terminal area must be covered to provide sufficient protection against unauthorized access to live parts. This is ensured by installing the device in the control cabinet or distributor box. The device contains dangerous live components and high levels of stored energy. To ensure that the device can be operated safely and all functions can be used, please read these instructions carefully. Caution: Never carry out work when the power is turned on, this is highly dangerous. PHOENIX CONTACT page 4 of 8 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 6. Installation 6.1. Mounting The power supply can be snapped onto all DIN rails according to EN 50022-35. The device must be mounted horizontally (input terminal blocks facing downwards). Installation Dimensions - To ensure sufficient convection, we recommend a minimum spacing of 5 cm (1.969 in.) to other modules above and below the device. - + + - - + C D K O - MINI POWER - - + OU - T D + DC OK C 24 + V1 A 22 .5-2 8 V D.5 C DC OK UT INP : 0V AC 0-24 z 10 0H : 50-6 nge4V a R 6 85-2-0.2A 0.4 C/1 4D C/2 C 60 40A 0 + 0 F ... 00-2 84 - 25 ... + 14 S-1 38 I-P : 29 - 13 RE MINer No. ply TU RA up Ord MPE rS TE e w ION AT Po -25 RM LOGY NO T INFO EN T CH U TE UIPM TP EQ OU LS AL OVA DUSTRIL C PR ns D IN NTROENT io AP ct ns COUIPM 24V st rum ai EQ n in 43KA 1%A om tio g to D al la tin ct.c 143 u U TE LIS ww st ec onta d inco nn nixc R ea fo re be phoe te w.in rf ace. : V DC -350A 90 -0.2 0.4 IN L(+ A C ) N 100 C -2 4 NC 0 V N() Installation depth 106 mm (4.173 in.) (+ DIN rail) 114.5 mm (4.508 in.) 106 mm (4.173 in.) - - MINI POWER 99 mm (3.898 in.) 22.5mm (0.886 in.) + DC OK - + - + OUT 24 V 1A 22.5-28.5 V DC DC OK IN 100-240 V AC L(+) NC NC N(-) 50 mm (1.969 in.) 199 mm (7.835 in.) 50 mm (1.969 in.) Figure 05 Figure 06 Mounting: Place the module with the DIN rail guideway on the top edge of the DIN rail and then snap it downwards. Mounting Removal Removal: Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail. Figure 07 PHOENIX CONTACT page 5 of 8 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 6.2. Connection of Various Types of Network: 100 - 240 V AC Networks TN-S network TN-C network TT network L PEN L N PE L N L N + - L + - N + - MINI L1 L2 L3 N PE L1 L2 L3 N L1 L2 L3 PEN L N MINI L N MINI MINI IT network L N L N +- L1 L2 L3 PE +- MINI L N MINI +- MINI +- Figure 08 Connection Cable: The device is equipped with COMBICON connectors. This reliable user-friendly connection method enables quick device connection and safe isolation of the electrical connection, if required. Only operate connectors when the power is switched off. - + V + 24 C D K O + 1 A N MINI-PS-100-240AC Power Supply OUTPUT A Order No.: 29 38 84 6 INPUT AC: NC 8 Protecting the Primary Side The device must be installed according to the specifications of EN 60 950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. Note that an all-pole disconnecting device must be provided for two-phase operation using two external conductors for a three-phase network. For example, primary side line protection could be used. Additional device protection is not required, as an internal fuse is present. C NC 7 6.3. Input (1, Figure 9) The 100 - 240 V AC connection is made using screw connections L and N. The device can be connected to single-phase AC networks or to two external conductors for three-phase networks (TN, TT or IT network according to VDE 0100 T300/IEC364-3) with nominal voltages of 100 - 240 V AC. - L 24V DC 100-240V 1% 50-60Hz 1A Range: 85-264V 0.4-0.2A DC: 90-350V 0.4-0.2A 7 mm (0.28 in.) 5 8. -2 DC .5 V C D K O Torque [Nm] [Ib in.] 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 25 - 14 0.5 - 0.6 4.4 - 5.3 For reliable and safe-to-touch connection: Strip 7 mm (0.28 in.) from the connector ends. AWG V ) 0 (24 N 0- C 10 N C A NC IN +) ( L 1 Input: 2 Output: 3 Signal: 22 MI - WE O IP N Flexible [mm2] 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 - TD U O R 1 The following cable cross sections can be connected: Solid [mm2] 0.2 - 2.5 0.2 - 2.5 0.2 - 2.5 2 3 4 Figure 09 (or equivalent). If the internal fuse is blown, this is most probably due to a device fault. In this case, the device should be checked in the factory. Recommended Fuse: Circuit breaker 6 A or 10 A, Characteristic B PHOENIX CONTACT page 6 of 8 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 6.4. Output (2, Figure 9) The 24 V DC connection is made using the "+" and "-" screw connections on the screw connection 2. The output voltage set upon delivery is 24 V DC. The output voltage can be adjusted from 22.5 to 28.5 V DC on the potentiometer 4. Output 24V DC Active signal output (3, Figure 10) The 24 V DC signal is between the "DC OK" and "-" connection terminal blocks and can be loaded with 20 mA maximum. This signal output indicates that the output voltage has fallen below 21.5 V DC when "active high" changes to "low". The DC OK signal is isolated from the power output. This ensures that a separate supply does not enter from devices connected in parallel. The 24 V DC signal can be connected directly to the logic input for evaluation. DC OK Protecting the Secondary Side: The device is electronic short-circuit-proof and idlingproof. In the event of an error, the output voltage is limited to a maximum of 35 V DC. It should be ensured that all output cables are the correct size for the maximum output current or have separate fuse protection. The secondary side cables should have large cross sections to keep voltage drops on the cables to a minimum. 24 V DC 20 mA + - - DC OK Figure 10 UOUT = 24 V UOUT [V] UN 24 Signaling The active DC OK switching output and the DC OK LED provide function monitoring. Green 5 "DC OK" LED5 Active DC OK switching output Meaning Status 1 ON Status 2 OFF U = +24 V (with reference to "-") Normal operation of the power supply UOUT > 21.5 V U=0V (with reference to "-") UOUT 21.5 V DC * Secondary load short circuit or overload * No mains voltage or device fault 7. Installation 7.1. Output Characteristic Curve The device can supply a nominal output current of 1 A up to an ambient temperature of 60C (140F). With an ambient temperature of up to 40C (104F) the device continuously supplies an output current of 1.3 A. At temperatures up to 60C (140F), the POWER BOOST provides a short-term output current of 1.3 A for a few minutes. With high loads, the working point demonstrates the U/I characteristic curve shown in Figure 11. On an overload or short circuit, the entire output current I BOOST is provided permanently at a reduced output voltage. < 60C (140F) < 40C (104F) 1 IN 1.3 IBOOST IOUT [A] Figure 11 Once the overload or short circuit has been removed, the entire set secondary voltage is available again. The U/I characteristic curve ensures that both heavy capacitive loads and devices with DC/DC converters can be supplied by MINI POWER in the input circuit without any problems. Connected fuses are reliably tripped. The selectivity in your system configuration is ensured at all times. PHOENIX CONTACT page 7 of 8 Power Supply, Primary Switch Mode, Narrow Design - MINI-PS-100-240AC/24DC/1 UOUT = 24 V Output current [A] 7.2. Temperature Response The device can supply a nominal output current of 1 A up to an ambient temperature of 60C (140F). With an ambient temperature of up to 40C (104F) the device continuously supplies an output current of 1.3 A. At temperatures up to 60C (140F), the POWER BOOST provides a short-term output current of 1.3 A for a few minutes. The output power must be decreased by 2.5% per Kelvin temperature increase for ambient temperatures above +60C (+140F). At ambient temperatures above +70C (+158F) or in the event of a thermal overload, the device reduces the output power to protect itself and returns to normal operation once it has cooled down. 1.3 1 0 0 20 40 60 Ambient temperature [C] Figure 12 7.3. Parallel Operation Devices of the same type can be connected in parallel to increase both redundancy and power. The default setting does not have to be adjusted. If the output voltage is adjusted, an even current distribution can be ensured by precisely setting all power supplies that are operated in parallel to the same output voltage. To ensure symmetrical current distribution we recommend that all cable connections from the power supply to the DIN rail are the same length and have the same cross section. Depending on the system, for parallel connection of more than two power supplies a protective circuit should be installed at each individual device output (e.g., decoupling diode or DC fuse). This means that in the event of a secondary device fault high return currents are avoided. MINI 24 V/1 A+ - http://www.phoenixcontact.com + - + - =1A + - MINI 24 V/1 A + - TNR: 5107937-00 Figure 13 MINI 24 V/1 + - 11/15/03 7.5. Power Increase The output current can be increased to n x IN where n is the number of devices connected in parallel. The parallel connection for power increase can be used to extend existing systems. A parallel connection is recommended if the power supply does not cover the current consumption of the most powerful load. Otherwise, the loads should be divided over independent individual devices. A maximum of five devices can be connected in parallel. MINI 24 V/1 + - =2A + - Figure 14 PHOENIX CONTACT page 8 of 8 PHOENIX CONTACT 7.4. Redundancy Operation Redundant connections are designed for supplying systems, which place particularly high requirements on operational safety. If a fault occurs in the primary circuit of device 1, device 2 automatically takes over the complete power supply without interruption and vice versa. For this purpose, the power supplies to be connected in parallel must be large enough that the total current requirements of all loads can be fully met by one power supply. External decoupling diodes are required for 100% redundancy.