SCHRACK
General Purpose
Panel/Plug-in Relays
Power Relay RM 8
n 2 pole 25 A, 2 form C (2 CO) contacts
n DC or AC coil
n Mechanical indicator
n Push-to-test button
n Chassis or DIN rail mount
Typical applications
Cleaning equipment, heating and cooling equipment.
Approvals
VDE Cert. No. 40003144, UL E214025,
Technical data of approved types on request.
Contact Data
Contact arrangement 2 form C (CO)
Rated voltage 250VAC (VDE) /415VAC (UL)
Max. switching voltage 415VAC
Rated current 25A
Limiting making current, 20ms max. 60A
Switching power 6000VA
Contact material AgNi90/10
Min. recommended contact load 24VDC/100mA
Frequency of operation,
with/without load, DC coil 360/6000h-1
Operate/release time max., DC coil 15/10ms
Bounce time max., form A/form B, DC coil 4/6ms
Contact ratings
Type Contact Load Cycles
IEC 61810
RM82/7 C (CO) 25 A, 250 VAC, cosφ=1 DC-coil, 65°C 10x103
RM82/7 C (CO) 25 A, 250 VAC, cosφ=1 AC-coil, 40°C 10x103
UL 508
RM82/7 A/B (NO/NC) 25 A, 277 VAC, general purpose, 50°C 6x103
RM8 A/B (NO/NC) 25 A, 415 VAC, resistive, 45°C 10x103
RM82/7 C (CO) 16 A, 415 VAC, resistive, 70°C 30x103
RM82/7 A/B (NO/NC) 240 VAC, 1phase, 2HP, 50°C 6x103
Mechanical endurance 10x106 operations
Coil Data
Coil voltage range 6 to 220VDC
12 to 400VAC
Operative range, IEC 61810 2
Coil insulation system according UL class 130 (B)
Coil versions, DC coil
Coil code Rated Coil Rated coil
STD LED PD3) LED+ voltage resistance power
bipolar PD3) VDC Ω±10%1)2) W
006 L06 0A6 LA6 6 32 1.1
012 L12 0B2 LB2 12 110 1.3
024 L24 0C4 LC4 24 475 1.2
048 L48 0E8 LE8 48 2000 1.2
060 L60 0G0 LG0 60 2850 1.3
110 M10 1B0 MB0 110 100001) 1.2
221 N21 2C1 NC1 220 400002) 1.2
Operate voltage, DC coil 75% of rated coil voltage
Release voltage, DC coil 10% of rated coil voltage
1) Coil resistance ±12%, 2) Coil resistance ±15%.
3) Protection diode PD; standard polarity: +A1 / -A2.
All figures are given for coil without pre-energization, at ambient temperature +23°C.