http://airpax.sensata.com/
PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series
282
PGFS Series
30 Amp Multi-Phase Permanent Series (Splice-In) GFCI
INTRODUCTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North
Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI
anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which
have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem
with an approved receptacle and enclosure.
Available with an operating voltage of 120/240 VAC dual voltage, 3Ø 120/208 VAC, 3Ø 240 VAC (certified to CSA 22.2 only), 3Ø 208 VAC or
3Ø 277 VAC (UL 1053 compliant), all units have 18” splicing leads and a 3/4” NPT fitting to allow connection to 3/4” PVC, EMT, burial and
flexible conduits. All units are MADE IN THE USA and are listed per UL 943 and CSA 22.2 No.144
• Powerandfaultstatusindicators
• Doubleinsulateduserinterface
• Industrialdesignforroughservice
• ChemicalandUVresistantenclosure
• cULusListedasaClassAGFCIperUL943and
CSA 22.2 No. 144
• 30ampconfigurationsin120/240VAC4-wire,
3Ø 120/208 VAC 5-wire, 3Ø 240 VAC 4-wire,
3Ø 208 VAC 4-wire, 3Ø 277 VAC 4-wire (UL 1053)
• NEMA4Xand6Pwetlocationrated(indoor/outdoor)
• Availableinautomaticormanualresetconfigurations1
SPECIFICATIONS
Listing Type cULus Listed Class A
UL 943
CSA 22.2 No. 144
Rated Supply Voltage 120/240 VAC Dual Voltage,
120/208 VAC 3Ø, 240 VAC 3Ø
(CSA only), 208 VAC 3Ø,
277 VAC 3Ø (UL 1053)
Rated Current Up to 30 Amps or rating of wiring
device and/or cable
Horse Power 1HP@120 VAC, 3HP@240 VAC
Trip Level 5mA +/–1mA
Operating Frequency 60Hz
Reset Type1Automatic or Manual
Phase Dual voltage and 3 phase
Response Time 25mS max
Operating Temperature –35°Cto66°C
Operating Voltage Range 85% to 110% of rated VAC
Let-Go Voltage 60%ofsupplyvoltage
Open Neutral Protection Trips upon loss of neutral
Grounded Neutral Protection Trips if ground and neutral touch
at load side
1. Manual configuration should be specified if automatic start-up after power
restoration of circuit power creates an unsafe condition.
2. Applicable models only
FEATURES
2 Voltage
C 120/240 VAC split Ø
4 120/208 VAC 3Ø
7 240 VAC 3Ø
8 208 VAC 3Ø
B 277 VAC 3Ø
3 Ampacity
3 30 amps
4 Reset Type
0 Manual
1 Automatic
PGFS - 4 3 0 0 5
Product Type
1
*Note: 1. Manual configuration should be specified if automatic power-up, after power restoration of circuit power, could create an unsafe condition.
15 Fault Output Options
0 None
6 Mounting Type
5 Panel mount
Flying Leads (Splice-in)
http://airpax.sensata.com/ PGFS Series - 30 Amp Multi-Phase Permanent (Splice-In) Series 283
APPLICATION OPPORTUNITIES:
Electrical wet locations
Power generators
Agricultural equipment
Outdoor electrical equipment
Cement cutting equipment
Portable electric heaters
Submersible pumps
Pipeline heaters
Automotive garages
Industrial part washers
Outdoor signage
De-icing equipment (roof heaters)
RELATED CODES
Confined Space OSHA29CFR1926.404(b)(1)(ii),
OSHA29CFR1926.405(a)(2)(ii)(G)
Construction Sites (NEC590.6)
Commercial Garages (NEC 511.12)
Outdoor Signs (NEC600.10)
Fountains & Water
Displays
(NEC680.58)
Spa & Hot Tubs (NEC680.40)
Marinas & Boat Yards (NEC 555.3)
DECISION TABLES
Ground Fault / Equipment Leakage