Description
• Fast acting, high breaking capacity
• 5mm x 20mm physical size
• Ceramic tube, nickel brass endcap construction
• Optional axial leads are .032" x 1.5" copper tinned
• Optional sleeve is flexible flouropolymer
(U.L. flammability rating VW-1).
• Designed to IEC 60127-2-1
1.1 In: ∆t less than or equal to 70°C, 125mA-3A
1.0 In: ∆t less than or equal to 70°C, 4A
Ordering
• Specify product code, option code and packaging code
Approvals
•UL Recognized, Guide JDYX2, File E75865,
50mA and 315mA-6.3A
•Semko Approval 50mA, 200mA and 315mA-6.3A
•VDE Approval 1.25A-6.3A
•IMQ Approval 500mA, and 2.0A-6.3A
Dimensions
Drawing Not to Scale
5mm x 20mm Fuses
GDA Series, Fast Acting, Ceramic Tube
SPECIFICATIONS
Voltage Interrupting Rating Typical Typical
Product Code Rating at Rated Voltage (50Hz) Melting I2t (A2Sec) Voltage
AC AC/DC AC Drop (mV)‡
GDA-50mA 250V 1500A 0.0017 9000
GDA-63mA 250V 1500A 0.0005 3300
GDA-80mA 250V 1500A 0.0011 2600
GDA-100mA 250V 1500A 0.0018 2300
GDA-125mA 250V 1500A 0.0037 1900
GDA-160mA 250V 1500A 0.008 1600
GDA-200mA 250V 1500A 0.020 1350
GDA-250mA 250V 1500A 0.027 1300
GDA-315mA 250V 1500A 0.010 1400
GDA-400mA 250V 1500A 0.018 1200
GDA-500mA 250V 1500A 0.038 1050
GDA-630mA 250V 1500A 0.064 1200
GDA-800mA 250V 1500A 0.097 490
GDA-1A 250V 1500A 0.480 230
GDA-1.25A 250V 1500A 0.9 200
GDA-1.6A 250V 1500A 1.9 180
GDA-2A 250V 1500A 2.0 205
GDA-2.5A 250V 1500A 3.9 190
GDA-3.15A 250V 1500A 8.1 160
GDA-4A 250V 1500A 14 160
GDA-5A 250V 1500A 25 155
GDA-6.3A 250V 1500A 48 150
‡Typical Voltage Drop (Voltage drop was measured at 20°C ambient temperature at rated current)
ELECTRICAL CHARACTERISTICS
1.5 In 2.1 In 2.75 In 4 In 10 In
In min max min max min max max
50mA-3.15A 60 min 30 min 10 ms 2 sec 3 ms 300 ms 20 ms
4A-10A 60 min 30 min 10 ms 3 sec 3 ms 300 ms 20 ms