TPCDS - Telpower®Compact Fused Disconnect Switch
TPC - Telpower®Compact Fuse - Current Limiting
Ampere Ratings: 3-125A
Available Ratings: 3, 4, 5, 6, 7, 8, 10, 12, 15, 20, 25, 30,
40, 50, 60, 75, 90, 100, 125A
Voltage Rating: 80Vdc
Interrupting Rating: 100,000A
Agency Information:
UL Recognized (investigated to UL 1801) as a
disconnect switch for the interruption of load current
by means of withdrawing the fuse pullout.
Recognized to U.S. and Canadian requirements under the
component recognition program of Underwriters
Laboratories Inc.
Files E219046 and E56412.
General Information:
• Fusible solution for replacement of existing dc Telecom
circuit breakers.
• Compact size fused disconnect switch.
• AmpColor ID™ System for easy fuse replacement.
• Available in two disconnect switch profiles in addition to a
variety of terminal styles.
• Local and remote open fuse indication.
Local alarm indication provided by LED on TPC fuse.
• Remote alarm terminal available in three positions
commonly found in dc circuit protection devices.
• Recommended .75 inch center-to-center product spacing.
• Current-limiting capability
• Complete system coordination capability.
• Highest interrupting rating (100,000A) available
for dc circuit protection of this footprint.
• No venting of arc or molten metals and gases during
fuse opening.
• Fuse material: Black thermoplastic, UL rated 94 V-O,
170° C RTI.
• Housing material: Black thermoplastic, UL rated 94 V-O,
120° C RTI.
*Not investigated to Canadian Requirements.
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
CE logo denotes compliance with European Union Low
Voltage Directive (50-1000Vac, 75-1500Vdc). Refer
to Data Sheet: 8002 or contact Bussmann Application
Engineering for more information.
Catalog Number Description Ampere Rating
TPC-3 Compact Fuse 3A
TPC-4 Compact Fuse 4A
TPC-5 Compact Fuse 5A
TPC-6 Compact Fuse 6A
TPC-7 Compact Fuse 7A
TPC-8 Compact Fuse 8A
TPC-10 Compact Fuse 10A
TPC-12 Compact Fuse 12A
TPC-15 Compact Fuse 15A
TPC-20 Compact Fuse 20A
TPC-25 Compact Fuse 25A
TPC-30 Compact Fuse 30A
TPC-40 Compact Fuse 40A
TPC-50 Compact Fuse 50A
TPC-60 Compact Fuse 60A
TPC-75 Compact Fuse 75A
TPC-90 Compact Fuse 90A
TPC-100 Compact Fuse 100A
TPC-125 Compact Fuse 125A
TPCDS-BBE-1 Compact Disconnect 3-125A
TPCDS-BBE-2 Compact Disconnect 3-125A
TPCDS-BBE-3 Compact Disconnect 3-125A
TPCDS-BBM-1 Compact Disconnect 3-125A
TPCDS-BBM-2 Compact Disconnect 3-125A
TPCDS-BBM-3 Compact Disconnect 3-125A
TPCDS-BSE-1 Compact Disconnect 3-125A
TPCDS-BSE-2 Compact Disconnect 3-125A
TPCDS-BSE-3 Compact Disconnect 3-125A
TPCDS-BSM-1 Compact Disconnect 3-125A
TPCDS-BSM-2 Compact Disconnect 3-125A
TPCDS-BSM-3 Compact Disconnect 3-125A
TPCDS-SSE-1 Compact Disconnect 3-125A
TPCDS-SSE-2 Compact Disconnect 3-125A
TPCDS-SSE-3 Compact Disconnect 3-125A
TPCDS-SSM-1 Compact Disconnect 3-125A
TPCDS-SSM-2 Compact Disconnect 3-125A
TPCDS-SSM-3 Compact Disconnect 3-125A
TPCDS-D-BC1* Compact Disconnect 3-125A
TPCDS-D-BC2* Compact Disconnect 3-125A
TPCDS-D-CC1* Compact Disconnect 3-125A
TPCDS-D-SEC1* Compact Disconnect 3-125A
TPCDS-D-SEC2* Compact Disconnect 3-125A
TPCDS-D-SMC1* Compact Disconnect 3-125A
TPCDS-D-SMC2* Compact Disconnect 3-125A
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.This bulletin
is intended to clearly present comprehensive product data and provide technical infor mation that will help the end user with design applications. Bussmann reser ves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products.Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Bussmann®
Telpower®Compact Fused Disconnect Switch TPC & TPCDS
Telpower®DC Power Protection Systems
DIN Rail Fused Disconnect Switch
• 35mm DIN rail mountable
• Front access.
• Three terminal style configurations available (see below).
• Screw clamp accepts 10 to 1 AWG (6mm2 - 50mm2) wire.
• Two remote alarm terminal positions available.
Terminal Style (select one)
BB - Bullet contact on the line
Bullet contact on the load
BS - Bullet contact on the line
Stud terminal on the load
SS - Stud terminal on the line
Stud terminal on the load
Thread (select one)
M - Metric threads for panel mount
fasteners (M3) and stud (M5)
E - English threads for panel mount
fasteners (6-32) and stud (10-32)
Remote Alarm Terminal Distance
(select one)
1 - .645 inch from line terminal
2 - .970 inch from line terminal
3 - 1.285 inch from line terminal
Terminal Style (select one)
CC - Screw Clamp terminal on the line
Screw Clamp terminal on the load
BC - Bullet contact on the line
Screw Clamp terminal on the load
SEC - Stud terminal on the line
English threads for stud (10-32)
Screw Clamp terminal on the load
SMC -Stud terminal on the line
Metric threads for stud (M5)
Screw Clamp terminal on the load
Remote Alarm Terminal Location
(select one)
1 - Side ouput
(available on CC and BC terminal styles)
2 - Bottom output, .970 inch
from line terminal
(available on BC terminal style only)
Part Number System --
Compact Fused Disconnect Switch
To identify part number, replace block with appropriate suffix to
identify line and load terminals, thread type, and alarm terminal
distance.
TPCDS - TELPOWER® Compact Fused Disconnect Switch
Part Number System --
DIN Rail Fused Disconnect Switch
To identify part number, replace block with appropriate suffix
to identify line and load terminals, thread type if applicable,
and alarm terminal option.
TPCDS - TELPOWER® Compact Fused Disconnect
Switch D- DIN-Rail style product
TPCDS - - TPCDS - D -
Form No. TPC & TPCDS
Page 2 of 7
Data Sheet: 5023
3-26-03 SB03069
Compact Fused Disconnect Switch
• Bullet and / or stud terminals for line and load connections
(1.940 inch / 49.3 mm spacing).
• Front access with bullet terminals.
Rear access with stud terminals.
• Three terminal style configurations available (see below).
• Remote alarm terminal available in three positions common
to dc circuit protection devices.
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
Bussmann®
Telpower®Compact Fused Disconnect Switch TPC & TPCDS
Telpower®DC Power Protection Systems
Form No. TPC & TPCDS
Page 3 of 7
Data Sheet: 5023
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
3-26-03 SB03069
TPCDS Terminal Styles
Compact Fused Disconnect Switch
Line: Bullet Load: Bullet
Line: Bullet Load: Stud Line: Stud Load: Stud
TPC Fuse
Bussmann®
Telpower®Compact Fused Disconnect Switch TPC & TPCDS
Telpower®DC Power Protection Systems
Form No. TPC & TPCDS
Page 4 of 7
Data Sheet: 5023
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
3-26-03 SB03069
TPCDS-D Terminal Styles
DIN Rail Fused Disconnect Switch
Alarm Schematic
NOTES:
1. The Electronic Monitoring Circuit (EMC) is a high input
impedance device that will provide alarming for an
open-fuse condition.
2. Typical leakage current through the load when the EMC
is operational 2 mA.
3. The resistance, R, must be provided by the end-user to
limit the alarm output current to a maximum of 20 mA.
The value, R, should be calculated using the system
voltage value.
If remote alarm functionality is not required, the
END-USER CIRCUITRY
must still be supplied to
provide a resistive path to the return for the local
alarm to properly function.
4. The fuse is polarized to maintain proper orientation with
the switch housing. The line and load terminals are
identified on the switch housing.
5. Electrical integrity of the load must be maintained after
fuse has opened in order for the local and remote alarm
to properly function.
Line: Screw Clamp
Load: Screw Clamp
Line: Stud*
Load: Screw
Clamp
Line: Bullet*
Load: Screw
Clamp
*Note: TPCDS-D Bullet / Screw Clamp and Stud / Screw Clamp terminal styles are not intended for 35 mm
DIN-RAIL mounting and will require auxiliary mechanical securement (not provided) for mounting.
Bussmann®
Telpower®Compact Fused Disconnect Switch
AmpColor ID™ System
TPC & TPCDS
Telpower®DC Power Protection Systems
Form No. TPC & TPCDS
Page 5 of 7
Data Sheet: 5023
Telpower’s AmpColor IDTM System Is Easy to Use.
Each Amp rating is represented by a specific color.
Simply label new or existing panels with the appro-
priate AmpColor tags and post the AmpColor char t
nearby. Personnel can quickly and accurately refer-
ence the char t for the appropriate replacement fuse.
AmpColor IDTM tags
AmpColor ID™ Chart
included with each
box of ten TPC
fuses.
TPC Fuses: 3-125A
TPM Fuses: 3-30A
Reference Data Sheet: 5022
for TPM fuse specifications.
Twelve AmpColor
ID™ tags included
with each box of
ten TPC fuses.
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
3-26-03 SB03069
Bussmann®
Telpower®Compact Fused Disconnect Switch TPC & TPCDS
Telpower®DC Power Protection Systems
Form No. TPC & TPCDS
Page 6 of 7
Data Sheet: 5023
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
3-26-03 SB03069
Time-Current Characteristic Cur ve–Average Melt - 3-20 Amp
Bussmann®
Telpower®Compact Fused Disconnect Switch TPC & TPCDS
Telpower®DC Power Protection Systems
Form No. TPC & TPCDS
Page 7 of 7
Data Sheet: 5023
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
3-26-03 SB03069
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.This bulletin
is intended to clearly present comprehensive product data and provide technical infor mation that will help the end user with design applications. Bussmann reser ves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products.Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Time-Current Characteristic Cur ve–Average Melt - 25-125 Amp