I/O Modules
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Manual Override Output Modules
SPECIFICATIONS: All Modules*
Output Specifications
Load Current Range (rms): 0.03 to 3.5
Amps, Maximum current is derated as shown
in Figure 1.
Maximum Surge Current (peak): 80 Amps
at 60 Hz, 1 cycle as qualified by Figure 2 for
AC outputs. 5 Amp maximum for 1 second for
DC outputs.
Turn-on Time (60 Hz): 8.3 mSec maximum
for AC outputs. 20 µSec maximum for DC
outputs.
Turn-off Time (60 Hz): 8.3 mSec maximum
for AC outputs. 50 µSec maximum for DC
outputs.
ON State Voltage Drop (peak): 1.5 volts
max.
Power Dissipation: 1.0 Watt/Amp typical
General Characteristics
Isolation Voltage Field to Logic: 4000 Vac
(rms) minimum
Vibration: 20 G's peak or .06” double amplitude
10–2000 Hz per MIL–STD–202, Method 204,
Condition D
Type/Function Grayhill Part Number
AC Outputs
SPECIFICATIONS: By Part Number
DC Outputs
Grayhill Part Number
G5, Zero Voltage Turn On, Manual Override 70G-OAC5MA 70G-OAC5AMA 70G-OAC24MA 70G-OAC24AMA
Specifications Units
Nominal Line Voltage Vac 120 240 120 240
Load Voltage Range Vac 24-140 24-280 24-140 24-280
Minimum Peak Blocking Voltage Volts 400 600 400 600
Maximum Off-state Leakage @ 60Hz mA, rms 2 4 2 4
Nominal Logic Voltage (Vcc) Vdc 5 5 24 24
Logic Voltage Range Vdc 4-6 4-6 18-32 18-32
Max. Logic Supply Current @ Nominal Vcc mA 20 20 8 8
Nominal Input Resistance (Rx) Ω100 100 2700 2700
Minimum Drop-Out Voltage Vdc 1 1 1 1
Maximum Reverse Logic Voltage Vdc -5 -5 -5 -5
Maximum Zero Voltage Offset (Vpeak) 8 8 8 8
Frequency Range (Hz) 25-70 25-70 25-70 25-70
70G-ODC5MA 70G-ODC24MA
Maximum Line Voltage Vdc 60 60
Load Voltage Range Vdc 3-60 3-60
Maximum Off-state Leakage @ 60 Vdc mA 1.5 1.5
Maximum Turn-on Time µSec 20 20
Maximum Turn-off Time µSec 50 50
Nominal Logic Voltage (Vcc) Vdc 5 24
Logic Voltage Range Vdc 4-6 18-32
Max. Logic Supply Current
@ Nominal Vcc mA 13 9
Nominal Input Resistance (Rx) Ω150 2700
Minimum Drop-Out Voltage Vdc 1 1
Maximum Reverse Logic Voltage Vdc -5 -5
Maximum Clamping Voltage Vdc 80 80
Available from your local Grayhill Distributor.
For prices and discounts, contact a local Sales
Office, an authorized local Distributor or Grayhill.
Mechanical Shock: 1500 G's 0.5 mS half-
sine per MIL–STD–202, Method 213,
Condition F
Storage Temperature Range:
-40°C to +125°C
Operating Temperature Range:
-40°C to +100°C
Type/Function
G5 Manual Override
Specifications Units
*Specifications apply over operating temperature range unless noted otherwise.
I/O
13