- 83 -
All Data Subject To Change Without Notice www.andersonpower.com
| SB®350 CONNECTOR SPECIFICATIONS |
Mechanical
Wire Size Range AWG mm²
Wire Contacts with Bushings 1/0 to 350 mcm 53.5 to 150
Max. Wire Insulation Diameter in. mm
1.100 27.900
Operating Temperature ² °F °C
Standard -4° to 221° -20° to 105°
Chemical Resistant -40 to 221° -40° to 105°
Mating Cycles No Load by Plating Silver (Ag)
Wire and Busbar Contacts 10,000
Avg. Mating / Unmating Force Lbf. N
2 Pole 30 133
Min. Contact / Spring Retention Force
lbf 150
N 667
Electrical
Current Rating Amperes 1 UL 1977 CSA
Wire to Wire (4/0 AWG) 450
Wire to Wire (350 mcm) 500 325
Voltage Rating AC/DC
UL 1977 600
Dielectric Withstanding Voltage
Volts AC 2,200
Avg. Mated Contact Resistance Milliohms 1
2 1/2” of 300mcm wire 0.050
Hot Plug Current Rating Amperes - Wire & Busbar
250 cycles at 120V DC 100A
Materials
Housing
Standard Plastic Resin Polycarbonate
Chem. Resistant Resin Polycarbonate / PBT blend
Contact Retention Spring Stainless Steel
Housing Flammability Rating
UL94 V-0
Glow Wire 960°C (GWFI) / 800°C (GWIT)
Wire & Busbar Contacts 4
Base Copper Alloy
Plating Silver
Contact Termination Methods
Crimp ³ Wire Contacts
Hand Solder Wire Contacts
Wrench / Socket Busbar Contacts
NOTE 1: See IEC 60664-1 for working voltage.
¹ Based on: 105°C rated or better cable of the largest size, Properly calibrated APP
recommended tooling, and a 25°C ambient temperature. UL rating not to exceed the
maximum operating temperature. CSA rating below a 30°C temperature rise.
² Limited by the thermal properties of the connector plastic housing.
³ Use APP recommended tooling only. Alternate tools may adversely affect the
performance of our connectors along with UL and CSA recognition.
4 Has not been tested by UL.
SECTION 3
SB® 350
See Busbar contact drawing on
website for further detail.
B[ 22.3 ]
0.88
[ 2.5 ]
0.10
[ 131.7 ]
5.19
[ 17.0 ]
0.67
# 3/8 - 16 THD
SB®350 Silver Plated Busbar Contacts
Use 2 busbar contacts per housing to provide a quick disconnect input or output busbar
connection. Busbar contacts are for mating with wire contacts only. Part number 350BBS
includes lock nuts. Locknuts must be ordered separately for B01998P1.
Mating
Type Thread Force - Loose Piece Part Numbers -
Minimum Quantity .................. 50 10 .............
Busbar 3/8-16 High B01998P1 350BBS
Lock Nut 3/8-16 - H1216P9 110G73
NOTE: Has not been tested by UL.
NOTE 2: Refer to the Constructional Data form for additional
information on our website., www.andersonpower.com
Protection
Touch Safety with Wire Contacts
IEC 60529 IP10
Unmated
Mated
Connector
Series Configurations Creepage/Clearance
per IEC 60950-1
IIIa
Material
Group
SB®350 5.66 mm
5.66 mm
Attributes SB350
AMP Rating AC/DC 350
Voltage Rating AC/DC (Steady State) 500 V AC/DC (Operational)
Breaking Capacity - AMP Rating /Cycles 100 Amp / 10 cycles
Voltage Rating (Breaking Capacity) 125 VDC
Finger Safety - Mated only IEC 60529 - IP20
Wire Size tested 120 mm²
Contact Series Tested 908
Climatic Testing (Cold,Heat & MFG) IEC 60512 Test -11j, 11i & 11g,
Cycle Life IEC 60512 Test 9a - 5000 Cycles
Mechanical Strength Impact IEC 60512-5 @ 29.5 Inches - dropped 8 times
Temperature Range -20 °C to 105 °C
-4 °F to 221 °F
| IEC INFORMATION |