6088171016 / 2084-17
Page 1 of 2
Technical Data
BERNSTEIN AG . Hans-Bernstein-Straße 1 . 32457 Porta Westfalica . www.bernstein.eu
Technical modifications and errors excepted.
The technical datasheet corresponds to the technical state as of 2017-02-23 and will not be removed in case of changes.
Plastic bodied limit switch
Series TI2
Operating symbol
Operating diagram
Electrical Data
Rated insulation voltage Ui250 V AC
Conv. thermal current Ithe 10 A AC / 2,5 A DC
Rated operational voltage Ue240 V AC; 250 V DC
Utilization category AC-15, Ue/Ie 240 V / 3 A; DC-13, Ue/Ie 250 V / 0,27 A
Direct opening action pacc. to IEC/EN 60947-5-1, Annex K
Short-circuit protective device Fuse 6 A gG
Protection class II, totally insulated
Description TI2-SU1Z HW RO13,5 Article number 6088171016
Tolerance:
Operating point ± 0,25 mm;
Actuating force ± 10 %
On Off
Fixed positioning with
e.g. fixing screw M5
according to the standard
DINENISO4762.
6088171016 / 2084-17
Page 2 of 2
Technical Data
BERNSTEIN AG . Hans-Bernstein-Straße 1 . 32457 Porta Westfalica . www.bernstein.eu
Technical modifications and errors excepted.
The technical datasheet corresponds to the technical state as of 2017-02-23 and will not be removed in case of changes.
Mechanical data
Enclosure Thermoplastic, glass fibre reinforced (UL 94-V0)
Cover Thermoplastic, glass fibre reinforced (UL 94-V0)
Actuator Roller (thermoplastic)
Ambient air temperature -30 °C ... +80 °C
Contact type 1 NC, 1 NO (Zb)
Mechanical life 3 x 106 operating cycles
Switching frequency ≤ 100 / min.
Assembly 2 x M4 or 2 x M5 fixed position for safety applications
Connection 4 screw connections (M3,5)
Conductor cross-sections Solid: 0,5 ... 1,5 mm² or
Litz wire with ferrules: 0,5 ... 1,5 mm²
Cable entrance 1 x M16 x 1,5
Weight ≈ 0,05 kg
Installation position operator definable
Protection type IP65 acc. to EN 60529; DIN VDE 0470 T1
Standards
VDE 0660 T100, DIN EN 60947-1, IEC 60947-1
VDE 0660 T200, DIN EN 60947-5-1, IEC 60947-5-1
DIN EN ISO 13849-1
EU Conformity
acc. to directive 2014/35/EU
Notes
The degree of protection (IP code) specified applies solely to a property closed cover and the use of an equivalent cable gland
with adequate cable.
Actuation
The actuating device is preferably started from 2 sides.
By loosening the 4 screws the actuation assembly can be rotated in 90 degree increments such that 4 actuation
directions are possible. The actuation assembly is to be again fastened to the housing using the 4 screws.
Approvals
CCSAUS, A300, Q300 (same polarity)
UL
CCC
ID for safety engineering
B10d 6 x 106 cycles