Low-PeakTM Class CC LP-CC -- 600Vac/300Vdc, 12-30A Time-Delay Fuses Dimensions - in 1.5" ( 0.031) (38.1mm) Description: Ultimate protection Class CC current-limiting, time-delay fuses. Time-delay - 12 seconds (minimum) at 200% of rated current. Catalog Symbol: LP-CC-(amp) Ratings: Volts -- 600Vac, -- 300Vdc (12-2810A, 20-30A) -- 150Vdc (3-15A) Amps -- 12-30A IR -- 200kA Vac RMS Sym. -- 20kA Vdc Agency Information: CE, Std. 248-4, Class CC, UL Listed, Guide JDDZ, File E4273 CSA Certified; Class 1422-02, File 53787 Catalog Numbers (amps) LP-CC-12 LP-CC-610 LP-CC-810 LP-CC-1 LP-CC-118 LP-CC-114 LP-CC-1410 LP-CC-112 LP-CC-1610 LP-CC-1810 LP-CC-2 LP-CC-214 LP-CC-212 LP-CC-2810 LP-CC-3 LP-CC-3210 LP-CC-312 LP-CC-4 LP-CC-412 LP-CC-5 LP-CC-5610 Carton Quantity and Weight Amp Rating 0-30 LP-CC-6 LP-CC-614 LP-CC-7 LP-CC-712 LP-CC-8 LP-CC-9 LP-CC-10 LP-CC-12 LP-CC-15 LP-CC-20 LP-CC-25 LP-CC-30 0.41" ( 0.005) (10.3mm) Features: * A superior all-purpose, space-saving branch circuit fuse that meets most protection requirements up to 30A * Very compact; physical size is only 1332" x 112" (10.3 x 38.1mm) with" rejection tip * The unique yellow color makes it easy to tell that the correct fuse type is installed * Faster response to damaging short-circuit currents and higher interrupting rating than mechanical overcurrent protective devices * 200kA interrupting rating for available fault current in today's large capacity systems and helps ensure that future growth will not obsolete the protection system * Time-delay characteristic avoids unwanted fuse openings from surge currents while fast response speed under shortcircuit conditions provides a high degree of current limitation * The LP-CC fuse can be sized close to full load ratings for maximum overload and short-circuit protection * Can be used where either a time-delay or a fast-acting fuse is needed, making selection easier and reducing spare fuse inventories for substantial cost reduction * Superior protection for small horsepower motor circuits * Proper sizing can provide "no damage" Type "2" coordinated protection for NEMA and IEC motor controllers * Motors receive maximum protection against burnout from overloads and single-phasing Recommended Fuse Blocks and Holders Fuse Amps 0-30 Carton Qty. 10 0-30 0-30 0-30 1-Pole 2-Pole Open Blocks BC6031_ BC6032_ DIN-Rail Holders CHCC1D_ CHCC2D_ -- -- -- -- -- -- Panel Mount Holders HPS -- HPF -- In-Line Holders -- HEX HEZ -- 3-Pole BC6033_ CHCC3D_ OPM-NG-_ OPM-1038_ OPM-1038_SW -- -- -- -- For additional information on the Class CC fuse blocks and holders, see data sheets: * Open Blocks # 1105 (BC Series) * DIN-Rail Holders # 3185 (CHCC), # 1109 (OPM), # 1102 (OPM-1038), 1103 (OPM-1038_SW), * Panel Mount Holders # 2113 (HPS), # 2114 (HPF) * In-Line Holders # 2126 (HEX), # 2130 (HEZ) 0713 BU-SB13732 Page 1 of 3 Data Sheet # 1023 Low-PeakTM Class CC LP-CC -- 600Vac/300Vdc, 12-30A Time-Delay Fuses 3-1/2 4 4-1/2 6 8 10 12 15 20 25 30 AMP RATING 3 200 6/10 8/10 1 1-1/4 1/2 Time-Current Curves - Average Melt 100 TIME IN SECONDS 10 1 0713 BU-SB13732 Page 2 of 3 1,000 CURRENT IN AMPs 100 10 0.4 0.01 1 0.1 Data Sheet # 1023 Low-PeakTM Class CC LP-CC -- 600Vac/300Vdc, 12-30A Time-Delay Fuses AMP RATING Current-Limitation Curves 3,000 2,000 30 25 20 15 1,000 800 600 500 400 2-8/10 300 1-1/4 200 100 80 60 50 40 30 2,000 800 1,000 400 500 600 300 200 80 100 40 50 60 10 10 30 20 20 INSTANTANEOUS PEAK LET-THROUGH CURRENT IN AMPS 4,000 PROSPECTIVE SHORT-CIRCUIT CURRENT-SYMMETRICAL RMS AMPS Current-Limiting Effects Prosp. Let-Through Current S.C.C. (Apparent RMS Symmetrical Vs. Fuse Rating) 114A 2810A 15A 20A 25A 1000 100 135 240 305 380 3000 140 210 350 440 575 5000 165 255 420 570 690 10,000 210 340 540 700 870 20,000 260 435 680 870 1090 30,000 290 525 800 1030 1300 40,000 315 610 870 1150 1390 50,000 340 650 915 1215 1520 60,000 350 735 1050 1300 1650 80,000 390 785 1130 1500 1780 100,000 420 830 1210 1600 2000 200,000 525 1100 1600 2000 2520 30A 435 580 710 1000 1305 1520 1700 1820 1980 2180 2400 3050 NOTE: To calculate Ip (Ipeak) multiply IRMS value by 2.3. The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. 0713 BU-SB13732 Page 3 of 3 Data Sheet # 1023