0713 BU-SB13732 Page 1 of 3 Data Sheet # 1023
Low-Peak™ Class CC
LP-CC — 600Vac/300Vdc, 1⁄2-30A Time-Delay Fuses
Description: Ultimate protection Class CC current-limiting,
time-delay fuses. Time-delay – 12 seconds (minimum) at
200% of rated current.
Catalog Symbol: LP-CC-(amp)
Ratings:
Volts — 600Vac,
— 300Vdc (1⁄2-28⁄10A, 20-30A)
— 150Vdc (3-15A)
Amps — 1⁄2-30A
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, Std. 248-4, Class CC, UL Listed, Guide JDDZ, File E4273
CSA Certified; Class 1422-02, File 53787
Catalog Numbers (amps)
LP-CC-1⁄2LP-CC-11⁄2LP-CC-3 LP-CC-6 LP-CC-12
LP-CC-6⁄10 LP-CC-16⁄10 LP-CC-32⁄10 LP-CC-61⁄4LP-CC-15
LP-CC-8⁄10 LP-CC-18⁄10 LP-CC-31⁄2LP-CC-7 LP-CC-20
LP-CC-1 LP-CC-2 LP-CC-4 LP-CC-71⁄2LP-CC-25
LP-CC-11⁄8LP-CC-21⁄4LP-CC-41⁄2LP-CC-8 LP-CC-30
LP-CC-11⁄4LP-CC-21⁄2LP-CC-5 LP-CC-9
LP-CC-14⁄10 LP-CC-28⁄10 LP-CC-56⁄10 LP-CC-10
Carton Quantity and Weight
Amp Rating Carton Qty.
0-30 10
Features:
• A superior all-purpose, space-saving branch circuit fuse that
meets most protection requirements up to 30A
• Very compact; physical size is only 13⁄32” x 11⁄2”
(10.3 x 38.1mm) with” rejection tip
• The unique yellow color makes it easy to tell that the correct
fuse type is installed
• Faster response to damaging short-circuit currents and
higher interrupting rating than mechanical overcurrent
protective devices
• 200kA interrupting rating for available fault current in today's
large capacity systems and helps ensure that future growth
will not obsolete the protection system
• Time-delay characteristic avoids unwanted fuse openings
from surge currents while fast response speed under short-
circuit conditions provides a high degree of current
limitation
• The LP-CC fuse can be sized close to full load ratings for
maximum overload and short-circuit protection
• Can be used where either a time-delay or a fast-acting fuse
is needed, making selection easier and reducing spare fuse
inventories for substantial cost reduction
• Superior protection for small horsepower motor circuits
• Proper sizing can provide “no damage” Type “2”
coordinated protection for NEMA and IEC motor controllers
• Motors receive maximum protection against burnout from
overloads and single-phasing
Recommended Fuse Blocks and Holders
Fuse Amps 1-Pole 2-Pole 3-Pole
Open Blocks
0-30 BC6031_ BC6032_ BC6033_
DIN-Rail Holders
CHCC1D_ CHCC2D_ CHCC3D_
0-30 ——OPM-NG-_
——OPM-1038_
——OPM-1038_SW
Panel Mount Holders
0-30 HPS ——
HPF ——
In-Line Holders
0-30 — HEX —
HEZ ——
For additional information on the Class CC fuse blocks and
holders, see data sheets:
• Open Blocks # 1105 (BC Series)
• DIN-Rail Holders # 3185 (CHCC), # 1109 (OPM),
# 1102 (OPM-1038), 1103 (OPM-1038_SW),
• Panel Mount Holders # 2113 (HPS), # 2114 (HPF)
• In-Line Holders # 2126 (HEX), # 2130 (HEZ)
1.5" (± 0.031)
(38.1mm)
0.41" (± 0.005)
(10.3mm)
Dimensions - in