I/O MODULE G4 DIGITAL DC OUTPUT DATA SHEET Form 254-990215 Description Opto 22's G4 DC output modules are used to control or switch DC loads. Each module provides up to 4,000 Vrms of optical-isolation between field devices and control logic. The G4ODC5MA is a special module featuring a manualon/manual-off/automatic switch, ideal for diagnostic testing of control applications. Typical applications for DC output modules include switching loads such as DC relays, solenoids, motor starters, lamps, and indicators. page 1/3 Part Number Description G4ODC5 G4 DC Output 5-60 VDC, 5 VDC Logic G4ODC5A G4 DC Output 5-200 VDC, 5 VDC Logic G4ODC5MA G4 DC Output 5-60 VDC, 5 VDC Logic With Manual/Auto Switch G4ODC15 G4 DC Output 5-60 VDC, 15 VDC Logic G4ODC24 G4 DC Output 5-60 VDC, 24 VDC Logic G4ODC24A G4 DC Output 5-200 VDC, 24 VDC Logic Features * * * * * * * * * 4,000 Vrms optical-isolation Built-in LED status indicator Logic levels of 5, 15, and 24 VDC Removable fuse Ability to withstand one-second surge of 5 amps Operating temperature: -30 C to 70 C UL recognized, CSA certified, CE approved Passes NEMA Showering Arc Test (ICS 2-230) Meets IEEE Surge Withstand Specification (IEEE-472) Opto 22 * 43044 Business Park Drive * Temecula, CA 92590 * Phone: (909) 695-3000 * (800) 321-OPTO * Fax: (909) 695-3095 * Internet: www.opto22.com Inside Sales: (800) 452-OPTO * Product Support: (800) TEK-OPTO * (909) 695-3080 * Fax: (909) 695-3017 * E-mail: support@opto22.com * FaxBack: (800) 474-OPTO Dimension and specifications are subject to change. All products and/or company names throughout this data sheet are generally trademarks or registered trademarks of their respective companies. I/O MODULE G4 DIGITAL DC OUTPUT DATA SHEET page 2/3 Form 254-990215 Specifications Units G4ODC5* G4ODC5A* G4ODC5MA* G4ODC15 G4ODC24 G4ODC24A Maximum line voltage VDC 60 200 60 60 60 200 Output voltage range VDC 5-60 5-200 5-60 5-60 5-60 5-200 --- --- Diagnostic switch --- --- --- Key feature Current rating: at 45C ambient at 70C ambient A A 3 2 1 0.55 3 2 3 2 3 2 1 0.55 Isolation input-to-output Vrms 4,000 4,000 4,000 4,000 4,000 4,000 Off-state leakage at maximum voltage mA 1 2 1 1 1 2 Control resistance (RC in schematic) 220 220 220 1K 2.2K 2.2K One-second surge A 5 5 5 5 5 5 Turn-on time s 50 100 50 50 50 100 Turn-off time s 50 750 50 50 50 750 Output voltage drop maximum peak V 1.6 1.6 1.6 1.6 1.6 1.6 Nominal logic voltage VDC 5 5 5 15 24 24 Logic voltage range VDC 4-8 4-8 4-8 10.5-16 19.5-32 19.5-32 Logic pickup voltage VDC 4 4 4 10.5 19.5 19.5 Logic dropout voltage VDC 1 1 1 1 1 1 Logic input current at nominal logic voltage mA 12 12 12 15 18 18 Temperature: Operating Storage C C -30 to +70 -30 to +85 -30 to +70 -30 to +85 -30 to +70 -30 to +85 -30 to +70 -30 to +85 -30 to +70 -30 to +85 -30 to +70 -30 to +85 Opto 22 * 43044 Business Park Drive * Temecula, CA 92590 * Phone: (909) 695-3000 * (800) 321-OPTO * Fax: (909) 695-3095 * Internet: www.opto22.com Inside Sales: (800) 452-OPTO * Product Support: (800) TEK-OPTO * (909) 695-3080 * Fax: (909) 695-3017 * E-mail: support@opto22.com * FaxBack: (800) 474-OPTO I/O MODULE G4 DIGITAL DC OUTPUT DATA SHEET page 3/3 Form 254-990215 Dimensions Schematics Opto 22 * 43044 Business Park Drive * Temecula, CA 92590 * Phone: (909) 695-3000 * (800) 321-OPTO * Fax: (909) 695-3095 * Internet: www.opto22.com Inside Sales: (800) 452-OPTO * Product Support: (800) TEK-OPTO * (909) 695-3080 * Fax: (909) 695-3017 * E-mail: support@opto22.com * FaxBack: (800) 474-OPTO