1
CSM_G3PB-2N_-3N_DS_E_2_1
Solid State Contactors (New Heat Sink Construction)
G3PB-2N/-3N
Space and working time saved with new heat
sink construction. Series now includes
480-VAC models to allow use in a greater
range of applications.
A comprehensive lineup that now includes 480-VAC models.
Slim design with 3-phase output and built-in heat sinks.
New heat sink construction with smaller mounting section.
DIN track mounting supported as standard. (Screw mounting is
also possible.)
Certified by UL, CSA, and VDE.
Refer to Safety Precautions for All Solid State
Relays.
Model Number Structure
Model Number Legend
1. Basic Model Name
G3PB: Solid State Relay
2. Rated Load Power Supply Voltage
2: 200 VAC
5: 480 VAC
3. Rated Load Current
15: 15 A
25: 25 A
35: 35 A
45: 45 A
4. Terminal Type
B: Screw terminals
5. Single-phase/3-phase and Number of Elements for 3-phase
2: 3-phase, 2-element models
3: 3-phase, 3-element models
6. 3-phase Type
N: DIN track mounting and built-in heat sink
H: No heat sink (“hockey puck” type)
7. Certification
VD: Certified by UL, CSA, and VDE
1234 56 7
G3PB-@@@-@@-@
G3PB-2N/-3N
2
Ordering Information
Solid State Contactors
Models with Built-in Heat Sinks
Note: The applicable load current depends on the ambient temperature. When ordering, specify the rated input voltage.
Models with Externally Attached Heat Sinks
Note: The applicable load current depends on the heat sink that is connected and the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 5.
Applicable
phase
Main circuit voltage Zero cross
function
Applicable load current
(with Class-1 AC resistive load)
Number of
poles
Model
3 100 to 240 VAC Yes 15 A 3 G3PB-215B-3N-VD DC12-24
2 G3PB-215B-2N-VD DC12-24
25 A 3 G3PB-225B-3N-VD DC12-24
2 G3PB-225B-2N-VD DC12-24
35 A 3 G3PB-235B-3N-VD DC12-24
2 G3PB-235B-2N-VD DC12-24
45 A 3 G3PB-245B-3N-VD DC12-24
2 G3PB-245B-2N-VD DC12-24
200 to 480 VAC 15 A 3 G3PB-515B-3N-VD DC12-24
2 G3PB-515B-2N-VD DC12-24
25 A 3 G3PB-525B-3N-VD DC12-24
2 G3PB-525B-2N-VD DC12-24
35 A 3 G3PB-535B-3N-VD DC12-24
2 G3PB-535B-2N-VD DC12-24
45 A 3 G3PB-545B-3N-VD DC12-24
2 G3PB-545B-2N-VD DC12-24
Applicable
phase
Main circuit voltage Zero cross
function
Applicable load current
(See note.)
Number of
poles
Model
3 100 to 240 VAC Yes 15 A 3 G3PB-215B-3H-VD DC12-24
2 G3PB-215B-2H-VD DC12-24
25 A 3 G3PB-225B-3H-VD DC12-24
2 G3PB-225B-2H-VD DC12-24
35 A 3 G3PB-235B-3H-VD DC12-24
2 G3PB-235B-2H-VD DC12-24
45 A 3 G3PB-245B-3H-VD DC12-24
2 G3PB-245B-2H-VD DC12-24
200 to 480 VAC 15 A 3 G3PB-515B-3H-VD DC12-24
2 G3PB-515B-2H-VD DC12-24
25 A 3 G3PB-525B-3H-VD DC12-24
2 G3PB-525B-2H-VD DC12-24
35 A 3 G3PB-535B-3H-VD DC12-24
2 G3PB-535B-2H-VD DC12-24
45 A 3 G3PB-545B-3H-VD DC12-24
2 G3PB-545B-2H-VD DC12-24
G3PB-2N/-3N
3
Specifications
Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (Common)
Main Circuit of Models with Built-in Heat Sinks
Note: 1. The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in
Engineering Data on page 5.
2. Applicable Load
Use the following formula to calculate the maximum total capacity of a heater load for a three-phase balanced load with delta connections.
Maximum load capacity = Load current × Load voltage ×
Example: 15 A × 200 V × = 5.196 W 5.1 kW
Example: 15 A × 400 V × = 10.392 W 10.3 kW
Main Circuit of Models with Externally Attached Heat Sinks
Note: The applicable load current depends on the heat sink that is connected and the ambient temperature.
For details, refer to Load Current vs. Ambient Temperature in Engineering Data on page 5.
Item Common
Rated voltage 12 to 24 VDC
Operating voltage range 9.6 to 30 VDC
Rated input current (Impedance) 10 mA max. (at 24 VDC)
Must operate voltage 9.6 VDC max.
Must release voltage 1 VDC min.
Insulation method Phototriac coupler
Operation indicator Ye l l o w L E D
Model
Item
G3PB-
215B-
3N-VD
G3PB-
215B-
2N-VD
G3PB-
225B-
3N-VD
G3PB-
225B-
2N-VD
G3PB-
235B-
3N-VD
G3PB-
235B-
2N-VD
G3PB-
245B-
3N-VD
G3PB-
245B-
2N-VD
G3PB-
515B-
3N-VD
G3PB-
515B-
2N-VD
G3PB-
525B-
3N-VD
G3PB-
525B-
2N-VD
G3PB-
535B-
3N-VD
G3PB-
535B-
2N-VD
G3PB-
545B-
3N-VD
G3PB-
545B-
2N-VD
Rated load voltage 100 to 240 VAC 200 to 480 VAC
Load voltage range 75 to 264 VAC 180 to 528 VAC
Applicable load
current
(See note 1.)
15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 45 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 45 A (at 25°C)
Minimum load cur-
rent
0.2 A 0.5 A
Inrush current re-
sistance
(peak value)
150 A
(60 Hz, 1 cy-
cle)
220 A
(60 Hz, 1 cy-
cle)
440 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
121 A2s 260 A2s 1260 A2s260 A
2s 1260 A2s
Applicable load
(resistive load,
AC1) (See note 2.)
5.1 kW max.
(at 200 VAC)
8.6 kW max.
(at 200 VAC)
12.1 kW max.
(at 200 VAC)
15.5 kW max.
(at 200 VAC)
12.5 kW max.
(at 480 VAC)
20.7 kW max.
(at 480 VAC)
29.0 kW max.
(at 480 VAC)
37.4 kW max.
(at 480 VAC)
Item
Model G3PB
-215B
-3H-VD
G3PB
-215B
-2H-VD
G3PB
-225B
-3H-VD
G3PB
-225B
-2H-VD
G3PB
-235B
-3H-VD
G3PB
-235B
-2H-VD
G3PB
-245B
-3H-VD
G3PB
-245B
-2H-VD
G3PB
-515B
-3H-VD
G3PB
-515B
-2H-VD
G3PB
-525B
-3H-VD
G3PB
-525B
-2H-VD
G3PB
-535B
-3H-VD
G3PB
-535B
-2H-VD
G3PB
-545B
-3H-VD
G3PB
-545B
-2H-VD
Rated load
voltage
100 to 240 VAC 200 to 480 VAC
Load voltage
range
75 to 264 VAC 180 to 528 VAC
Applicable
load current
(See note.)
15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 45 A (at 25°C) 15 A (at 40°C) 25 A (at 40°C) 35 A (at 25°C) 45 A (at 25°C)
Minimum load
current
0.2 A 0.5 A
Inrush
current
resistance
(peak value)
150 A (60 Hz,
1 cycle)
220 A (60 Hz,
1 cycle)
440 A (60 Hz, 1 cycle) 220 A (60 Hz, 1 cycle) 440 A (60 Hz, 1 cycle)
Permissible
I2t (half 60-Hz
wave)
121 A2s 260 A2s 1,260 A2s 260 A2s 1,260 A2s
Applicable
load (resistive
load, AC1)
Refer to Engineering Data on page 5.
3
3
3
G3PB-2N/-3N
4
Characteristics
Models with Built-in Heat Sinks
Note: The leakage current of phase S will be approximately times larger if the 2-element model is applied.
Models with Externally Attached Heat Sinks
Note: The leakage current of phase S will be approximately times larger if the 2-element model is used.
Item G3PB-
215B-
3N-VD
G3PB-
215B-
2N-VD
G3PB-
225B-
3N-VD
G3PB-
225B-
2N-VD
G3PB-
235B-
3N-VD
G3PB-
235B-
2N-VD
G3PB-
245B-
3N-VD
G3PB-
245B-
2N-VD
G3PB-
515B-
3N-VD
G3PB-
515B-
2N-VD
G3PB-
525B-
3N-VD
G3PB-
525B-
2N-VD
G3PB-
535B-
3N-VD
G3PB-
535B-
2N-VD
G3PB-
545B-
3N-VD
G3PB-
545B-
2N-VD
Operate time 1/2 of load power source cycle + 1 ms max.
Release time 1/2 of load power source cycle + 1 ms max.
Output ON
voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage
current
(See note.)
10 mA (at 200 VAC) 20 mA (at 480 VAC)
Insulation
resistance
100 M min. (at 500 VDC)
Dielectric
strength
2,500 VAC, 50/60 Hz for 1 min
Vibration
resistance
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) (Mounted to DIN track)
Shock resis-
tance
Destruction: 294 m/s2 (98 m/s2 with reverse mounting)
Ambient
operating
temperature
Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
Ambient
operating
humidity
Operating: 45% to 85%
Weight Approx.
1.25 kg
Ap-
prox.
1.45
kg
Ap-
prox.
1.25
kg
Ap-
prox.
1.65
kg
Ap-
prox.
1.45
kg
Ap-
prox.
2.0 kg
Ap-
prox.
1.65
kg
Approx.
1.25 kg
Ap-
prox.
1.45
kg
Ap-
prox.
1.25
kg
Ap-
prox.
1.65
kg
Ap-
prox.
1.45
kg
Ap-
prox.
2.0 kg
Ap-
prox.
1.65
kg
Certified
standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3); Certified by VDE
(From April 2001)
EMC Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Item
Model G3PB
-215B
-3H-VD
G3PB
-215B
-2H-VD
G3PB
-225B
-3H-VD
G3PB
-225B
-2HVD
G3PB
-235B
-3H-VD
G3PB
-235B
-2H-VD
G3PB
-245B
-3H-VD
G3PB
-245B
-2H-VD
G3PB
-515B
-3H-VD
G3PB
-515B
-2H-VD
G3PB
-525B
-3H-VD
G3PB
-525B
-2H-VD
G3PB
-535B
-3H-VD
G3PB
-535B
-2H-VD
G3PB
-545B
-3H-VD
G3PB
-545B
-2H-VD
Operate time 1/2 of load power source cycle + 1 ms max.
Release time 1/2 of load power source cycle + 1 ms max.
Output ON
voltage drop
1.6 V (RMS) max. 1.8 V (RMS) max.
Leakage
current
(See note.)
10 mA (at 200 VAC) 20 mA (at 480 VAC)
Insulation
resistance
100 M min. (at 500 VDC)
Dielectric
strength
2,500 VAC, 50/60 Hz for 1 min
Vibration
resistance
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
Shock
resistance
Destruction: 294 m/s2 (98 m/s2 with reverse mounting)
Storage
temperature
–30°C to 100°C (with no icing or condensation)
Ambient
operating
temperature
–30°C to 80°C (with no icing or condensation)
Ambient
storage
humidity
45% to 85%
Weight Approx. 300 g
3
3
G3PB-2N/-3N
5
Engineering Data
Load Current vs. Ambient Temperature
Models with Built-in Heat Sinks
30
25
20
10
8
0
Load current (A)
Ambient temperature (°C)
-30 -20
0 20 40 60 80 100 25
22
Derating curve under UL standard
G3PB-215B-3N-VD
G3PB-215B-2N-VD
G3PB-225B-3N-VD
G3PB-225B-2N-VD
G3PB-235B-3N-VD
G3PB-235B-2N-VD
30
25
15
20
10
7
0
Load current (A)
Ambient temperature (°C)
30 20 0 20 40 60 80 100
6
Derating curve under
UL standard
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 28 A is
applicable under the UL standard only with forced
air cooling by fan.
50
35
30
20
10
14
0
Load current (A)
Ambient temperature (°C)
40
8
28
30 20 0 20 40 60 80 100 25
Derating curve under UL standard
30
25
15
20
10
7
0
Load current (A)
Ambient temperature (°C)
30 20 0 20 40 60 80 100
6
Derating curve under
UL standard
30
25
20
10
8
0
Load current (A)
Ambient temperature (°C)
30 20 0 20 40 60 80 100 25
22
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 22 A is
applicable under the UL standard only with forced
air cooling by fan.
Derating curve under UL standard
G3PB-245B-3N-VD
G3PB-245B-2N-VD
G3PB-515B-3N-VD
G3PB-515B-2N-VD
G3PB-525B-3N-VD
G3PB-525B-2N-VD
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 42 A is
applicable under the UL standard only with forced
air cooling by fan.
Ambient temperature (°C)
50
45
30
20
10
18
0
40
30 20 0 20 40 60 80 100 25
12
42
Load current (A)
Derating curve under UL standard
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 42 A is
applicable under the UL standard only with forced
air cooling by fan.
Ambient temperature (°C)
50
45
30
20
10
18
0
40
30 20 0 20 40 60 80 100 25
12
42
Load current (A)
Derating curve under UL standard
G3PB-535B-3N-VD
G3PB-535B-2N-VD
G3PB-545B-3N-VD
G3PB-545B-2N-VD
Note: 1. Please use proper ventilation and cooling.
2. Please note that the derating curve above 28 A is
applicable under the UL standard only with forced
air cooling by fan.
50
35
30
20
10
14
0
Load current (A)
Ambient temperature (°C)
40
8
28
30 20 0 20 40 60 80 100 25
Derating curve under UL standard
G3PB-2N/-3N
6
Load Current vs. Ambient Temperature
Models without Built-in Heat Sinks
Input Voltage vs. Input Current and Input Voltage vs. Input Impedance
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
Note: Please use proper ventilation and cooling.
Ambient temperature (°C)
10
1.5
6
4
2
0
8
30 20 0 20 40 60 80 100 25
5
Load current (A)
Derating curve under UL standard
G3PB-215B-3H(-2H)-VD
G3PB-225B-3H(-2H)-VD
G3PB-515B-3H(-2H)-VD
G3PB-525B-3H(-2H)-VD
G3PB-235B-3H(-2H)-VD
G3PB-245B-3H(-2H)-VD
G3PB-535B-3H(-2H)-VD
G3PB-545B-3H(-2H)-VD
Note: Please use proper ventilation and cooling.
10
5
6
4
2
0
Load current (A)
Ambient temperature (°C)
8
1.5
30 20 0 20 40 60 80 100
Derating curve under UL standard
G3PB-225B-3(-2)H-VD
G3PB-525B-3(-2)H-VD
G3PB-215B-3(-2)H-VD
G3PB-515B-3(-2)H-VD
Input volta
g
e (V)
Input current (mA)
Input impedance (k)
Input current
Input impedance
Inrush current
Energized time (ms) Energized time (ms)
Inrush current
Energized time (ms)
Inrush current
G3PB-215B-3N/3H-VD
G3PB-215B-2N/2H-VD
G3PB-225B-3N/3H-VD
G3PB-225B-2N/2H-VD
G3PB-515B-3N/3H-VD
G3PB-515B-2N/2H-VD
G3PB-525B-3N/3H-VD
G3PB-525B-2N/2H-VD
G3PB-235B-3N/3H-VD
G3PB-235B-2N/2H-VD
G3PB-245B-3N/3H-VD
G3PB-245B-2N/2H-VD
G3PB-535B-3N/3H-VD
G3PB-535B-2N/2H-VD
G3PB-545B-3N/3H-VD
G3PB-545B-2N/2H-VD
G3PB-2N/-3N
7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
68
68
32.2
20 Six, M4
0.5
20
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
100
max.
80.5
max. 90
64
80 max.
14.6
64±0.3
90±0.3
Four, 4.5-dia. or M4
19.4
120 max.
30.5
max.
24
Two, R2.3
mounting
holes
Without Terminal Cover With Terminal Cover
A1
A2
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
A1
A2
Terminal Arrangement/Internal Connections
G3PB-2@5B-2N-VD
G3PB-215B-3N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-5@5B-2N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-515B-3N-VD
G3PB-215B-3N-VD
G3PB-215B-2N-VD
G3PB-225B-2N-VD
G3PB-515B-3N-VD
G3PB-515B-2N-VD
G3PB-525B-2N-VD
Mounting Hole Dimensions
120
max.
80.5
max. 110100
64
80 max.
68
68
32.2
20 Six, M5 (35 A type)
Six, M4 (25 A type)
0.5
20
Four, 8 dia.
Two, M3.5
24
Two, R2.3
mounting
holes
14.6
64±0.3
110±0.3
Four, 4.5-dia. or M4
19.4
120 max.
30.5
max.
Two, 4.6-dia. mounting holes
Without Terminal Cover With Terminal Cover
G
3PB-225B-3N-VD
G3PB-235B-2N-VD
G3PB-525B-3N-VD
G3PB-535B-2N-VD
Mounting Hole Dimensions
A1
A2
A1
A2
Terminal Arrangement/Internal Connections
G3PB-235B-2N-VD
G3PB-225B-3N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-535B-2N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-525B-3N-VD
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
G3PB-2N/-3N
8
140
max.
80.5
max. 130120
64
68
68
32.2
20
0.5
20
24
Two, R2.3
mounting
holes
14.6
64±0.3
130±0.3
19.4
30.5
max.
Two, 4.6-dia. mounting holes
Four, 8 dia.
120 max.
Four, 4.5-dia. or M4
Without Terminal Cover With Terminal Cover
Two, M3.5
Six, M5
80 max.
G3PB-235B-3N-VD
G3PB-245B-2N-VD
G3PB-535B-3N-VD
G3PB-545B-2N-VD
Mounting Hole Dimensions
A1
A2
A1
A2
Terminal Arrangement/Internal Connections
G3PB-245B-2N-VD
G3PB-235B-3N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-545B-2N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-535B-3N-VD
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
Input circuit
(+)
()
140
max.
80.5
max. 130120
64
68
68
32.2
20
0.5
20
24
Two, R2.3
mounting
holes
14.6
64±0.3
130±0.3
Four, 4.5-dia. or M4
19.4
30.5
max.
Four, 8 dia.
80 max.
120 max.
110 max.
Two, 4.6-dia. mounting holes
Without Terminal Cover With Terminal Cover
Two, M3.5
Six, M5
G3PB-245B-3N-VD
G3PB-545B-3N-VD
A1
A2
Terminal Arrangement/Internal Connections
G3PB-245B-3N-VD
L1/R
T1/U T2/V T3/W
L2/S L3/T L1/R
T1/U T2/V T3/W
L2/S L3/T
A1
A2
G3PB-545B-3N-VD
Input circuit
(+)
()
Input circuit
(+)
()
Mounting Hole Dimensions
G3PB-2N/-3N
9
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or
comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified)
from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR
FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER
WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS
IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT
SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's
application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the
products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product,
machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible
uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE
SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or
establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the
result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON
Warranty and Limitations of Liability.
ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.
2008.11
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/