Product catalogue | Electronics | Analogue signal conditioning | Temperature RTD - signal isolator/converter | PT100,
2-/3-/4-conductor temperature transducer | MCZ PT100/3 CLP
- 1 -
General ordering data
Order No. 8473000000
Part designation MCZ PT100/3 CLP -50C...+150C
Version Signal converter/disconnector, 4...20 mA (current
loop) , Tension clamp connection
EAN 4032248058273
Qty. 10 pc(s).
Input
Sensor PT100/2-/3-conductor (to IEC 751)
Temperature input range -50...+150 °C
Number of inputs 1
Output
Output current 4...20 mA (current loop)
Load resistance, current ≤ 600 Ω
Influence of line resistance Max. 0.006 K/Ω
Function 3-conductor connection
Product catalogue | Electronics | Analogue signal conditioning | Temperature RTD - signal isolator/converter | PT100,
2-/3-/4-conductor temperature transducer | MCZ PT100/3 CLP
- 2 -
Output
Accuracy Typical 0.2%, max. 0.5% of FSR
Linearization Yes
Step response time 10 ms
Temperature coefficient Max. ± 250 ppm/K
Number of outputs 1
General data
Function PT100
Input/Output PT100/ 4...20 mA (current loop)
Galvanic isolation Without isolation
Type of connection Tension clamp connection
Mounting rail TS 35
Voltage supply Max. 30 V/ min. 9 V + (20 mA x RL)
Ambient temperature (operational) 0 °C...+50 °C
Storage temperature -20 °C...+85 °C
Insulation coordination
Standards EN 50178, EN 60751, IEC751
EMC standards EMVG, EN 61000-6
Dimensions
Clamping range, max. 1.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, nom. 1.5 mm²
Length 91 mm
Height 63.2 mm
Width 6 mm
Approvals
Approvals institutes
Classifications
eClass 4.1 27-20-02-06
eClass 5.0 27-20-02-06
eClass 5.1 27-20-02-06
Similar products
Order No. Part designation Version
8425720000 MCZ PT100/3 CLP 0...100C Signal converter/disconnector, 4...20 mA (current loop) , Tension
clamp connection
8483680000 MCZ PT100/3 CLP 0...120C Signal converter/disconnector, 4...20 mA (current loop) , Tension
clamp connection
8604420000 MCZ PT100/3 CLP 0...150C Signal converter/disconnector, 4...20 mA (current loop) , Tension
clamp connection
Product catalogue | Electronics | Analogue signal conditioning | Temperature RTD - signal isolator/converter | PT100,
2-/3-/4-conductor temperature transducer | MCZ PT100/3 CLP
- 3 -
8473010000 MCZ PT100/3 CLP 0...200C Signal converter/disconnector, 4...20 mA (current loop) , Tension
clamp connection
8473020000 MCZ PT100/3 CLP 0...300C Signal converter/disconnector, 4...20 mA (current loop) , Tension
clamp connection
8604430000 MCZ PT100/3 CLP -40C...100C Signal converter/disconnector, 4...20 mA (current loop) , Tension