16 Specifications are subject to change without notice
Industrial Relay
Type RCP
Monostable
• 8 or 11-pin socket mounting
• 2 or 3 change over contacts
• Long life (minimun 100.000 electrical operations)
at 10 A 250 VAC /30 VDC
• Switching capacity 12 A (5x104cycles)
• AC coils 6 to 230 VAC
• DC coils 6 to 110 VDC
• Matched sockets available
• Standard with LED, Push with arm and Flag
• IP 40
• Conform to CE low voltage directive
• IMQ, UL, TÜV, CSA approved
RCP
Type
No. of pins
Contact code
Rated coil voltage
DC / AC
Product Description Ordering Key RCP 8 002 24 DC
Contact code
002
003
Contact rating
10 A
10 A
Contact configuration
2 change over contacts (DPDT {2-form C})
3 change over contacts (3PDT {3-form C})
Type Selection
The RCP relay can be used
for a wide range of industrial
applications.
Available in 2 or 3 change-
over contact configuration,
Octal or Undecal version.
At 20°C At 40°C
Nominal Pick-up Drop-out Pick-up Drop-out Coil
voltage voltage voltage voltage voltage resistance
VDC VDC VDC VDC VDC Ω
6 4.8 0.6 5.2 0.6 23.5 ±10%
12 9.6 1.2 10.3 1.3 95.0 ±10%
24 19.2 2.4 20.7 2.6 430.0 ±10%
48 38.4 4.8 41.4 5.1 1630.0 ±15%
60 45.0 6.0 48.6 6.4 3000.0 ±15%
100 80.0 10.0 86.4 10.8 6800.0 ±15%
110 88.0 11.0 95.0 11.8 6800.0 ±15%
Coil Characteristics, DC
At 20°C At 40°C
Nominal Pick-up Drop-out Pick-up Drop-out Coil
voltage voltage voltage voltage voltage resistance
VAC VAC VAC VAC VAC Ω
6 4.8 1.8 5.2 1.9 40.0 ±10%
12 9.6 3.6 10.3 3.8 160.0 ±10%
24 19.2 7.2 20.7 7.7 650.0 ±10%
48 38.4 14.4 41.4 15.5 2600.0 ±15%
115/120 88.0 36.0 95.0 38.8 11000.0 ±15%
230 176.0 72.0 190.0 77.7 11000.0 ±15%
Coil operating range: see diagram n° 1 pag. 18
Coil Characteristics, AC