General Purpose US Fuses
General Purpose US Fuses
GPUS65
Midget Fuses (10x38 US)
Time Delay
TRM
12/04
Ampere Reference Ampere Reference Ampere Reference Ampere Reference Ampere Reference Ampere Reference
Rating Number Rating Number Rating Number Rating Number Rating Number Rating Number
1/10 R217273 6/10 X222545 1-6/10 E216250 3 H213700 5-6/10 W218818 10 V218817
15/100 M223065 8/10 G201394 1-8/10 C216754 3-2/10 R214720 6 H219335 12 G219334
2/10 P212165 1 M214210 2 S200852 3-1/2 N214211 6-1/4 H219864 15 W222544
3/10 V215229 1-1/8 T215228 2-1/4 R211132 4 F216251 7 N223066 20 F212686
4/10 W217783 1-1/4 Q214719 2-1/2 T201911 4-1/2 D216755 8 T200853 25 Q213201
1/2 V217782 1-4/10 Y215738 2-8/10 H211653 5 G218299 9 V201912 30 Z215739
Standard Fuse Ampere Ratings, Reference Numbers
Ampere Catalog Ampere Catalog Ampere Catalog Ampere Catalog Ampere Catalog Ampere Catalog
Rating Number Rating Number Rating Number Rating Number Rating Number Rating Number
1/10 TRM1/10 6/10 TRM6/10 1-6/10 TRM1-6/10 3 TRM3 5-6/10 TRM5-6/10 10 TRM10
15/100 TRM15/100 8/10 TRM8/10 1-8/10 TRM1-8/10 3-2/10 TRM3-2/10 6 TRM6 12 TRM12
2/10 TRM2/10 1 TRM1 2 TRM2 3-1/2 TRM3-1/2 6-1/4 TRM6-1/4 15 TRM15
3/10 TRM3/10 1-1/8 TRM1-1/8 2-1/4 TRM2-1/4 4 TRM4 7 TRM7 20 TRM20
4/10 TRM4/10 1-1/4 TRM1-1/4 2-1/2 TRM2-1/2 4-1/2 TRM4-1/2 8 TRM8 25 TRM25
1/2 TRM1/2 1-4/10 TRM1-4/10 2-8/10 TRM2-8/10 5 TRM5 9 TRM9 30 TRM30
Standard Fuse Ampere Ratings, Catalog Numbers
Tri-onic®TRM time-delay midget fuses are rated
250 volts AC and are offered in 36 ampere ratings
from 1/10A to 30A. They have 12 seconds time
delay at 200% rating to provide supplemental
protection of small motors, small transformers and
other high inrush loads, plus many other 250 volt
applications. (Not for Branch Circuit Protection).
Features/Benefits
• Numerous ratings for a wide variety
of applications
• 250VAC rating in all sizes up to 30A
• Time delay for circuits with high inrush
currrent
• UltraSafe TM fuse holder: refer to Fuse Blocks
and Fuse Holders section for details,Catalog
Number and Reference Number
Ratings
• AC: 1/10 to 30A
250VAC, 10kA I.R.
Highlights
• Time Delay
• 250 VAC Rated
Applications
• Small Motors
• Small Transformers
• Lighting Circuits
• Control Circuits
Approvals
• UL Listed to Standard 248-14
• CSA Certified to Standard C22.2 No. 248.14