ELR 1…600AC…
103060_01_en PHOENIX CONTACT 2
Ordering Data
Technical Data
Load Relays With 24 V DC Input Voltage
Description Type Order No. Pcs./Pck.
Single-phase electronic load relay, input voltage: 24 V DC,
output current: 20 A
ELR 1-24DC/600AC/20 2297138 1
Single-phase electronic load relay, input voltage: 24 V DC,
output current: 30 A
ELR 1-24DC/600AC/30 2297154 1
Single-phase electronic load relay, input voltage: 24 V DC,
output current: 50 A
ELR 1-24DC/600AC/50 2297170 1
Load Relays With 230 V AC Input Voltage
Description Type Order No. Pcs./Pck.
Single-phase electronic load relay, input voltage: 230 V AC,
output current: 20 A
ELR 1-230AC/600AC/20 2297141 1
Single-phase electronic load relay, input voltage: 230 V AC,
output current: 30 A
ELR 1-230AC/600AC/30 2297167 1
Single-phase electronic load relay, input voltage: 230 V AC,
output current: 50 A
ELR 1-230AC/600AC/50 2297183 1
For marking systems and assembly material, see CLIPLINE catalog.
Input Data for Load Relays With 24 V DC Input Voltage (ELR 1-24DC/...)
Operating voltage range 4 V DC ... 32 V DC
Switching level
1 signal ("H")
0 signal ("L")
≥ 4 V DC
≤ 1 V DC
Input current at UN = 24 V DC Approximately 12 mA, typical
Transmission frequency at flimit (ohmic load) 25 Hz
Input circuit Operating voltage indicator (green LED)
Input Data for Load Relays With 230 V AC Input Voltage (ELR 1-230AC/...)
Operating voltage range 24 V AC ... 275 V AC
Switching level
1 signal ("H")
0 signal ("L")
≥ 22 V AC
≤ 6 V AC
Input current at UN = 24 V DC Approximately 17 mA, typical
Transmission frequency at flimit (ohmic load) 6 Hz
Input circuit Operating voltage indicator (green LED)
Output Data ELR 1.../20 ELR 1.../30 ELR 1.../50
Operating voltage range 42 V AC ... 660 V AC, 45/65 Hz
Periodic peak reverse voltage 1200 V
Maximum continuous current 20 A 30 A 50 A
Surge current 250 A (t = 10 ms) 400 A (t = 10 ms) 1900 A (t = 10 ms)
Minimum load current 350 mA 150 mA 150 mA
Residual voltage at maximum load current < 1.6 V
Leakage current when switched off < 3 mA
Maximum phase shift (inductive loads) cos ϕ = 0.5
Maximum load value I2 x t (t = 10 ms) 310 A2s 1800 A2s 18000 A2s
Output circuit RCV circuit