Protistor DCProtistor fuses DC fuses DC Ferrule Fuses 36x127 gR 1000V DC 1000 V DC gRB-gRC from 25 to 100 A Size 36x127 Dimensions 7 mini 127 o 36 o5 Weight : 299 g Trip force: 4.5N at 0 mm - 2.5N at 7 mm Main Characteristics Size 36x127 Current rating IN( A ) Breaking Capacity 25 32 40 50 63 80 100 1000 V 100 kA 20 ms 1000 V 100 kA 20 ms Watts loss 0.8 IN IN (W) (W) 5.3 6.4 6.5 8.7 10.5 11.9 13.2 9.4 11.5 11.6 15.4 18.8 21.5 24.1 Designation Reference Number Catalog Number CC 1051 CP gRB 36x127/25 CC 1051 CP gRB 36x127/32 CC 1051 CP gRB 36x127/40 CC 1051 CP gRB 36x127/50 CC 1051 CP gRC 36x127/63 CC 1051 CP gRC 36x127/80 CC 1051 CP gRC 36x127/100 H 083980 R 086495 G 089499 H 089500 J 089501 A 083651 Z 083650 FD36GB100V25T FD36GB100V32T FD36GB100V40T FD36GB100V50T FD36GC100V63T FD36GC100V80T FD36GC100V100T Minimum trip indicator operating voltage: 50 V See Fuse Blocks, Fuse Holders and Fuse clips Pack: 3 pieces SCDC10 12/04 Protistor DC fuses Protistor DC fuses DC Ferrule Fuses 36x127 gR 1000V DC gRB-gRC from 25 to 100 A Electrical characteristics DC applications data Peak arc voltage vs. working voltage L/R (ms) Um (V) 1 2000 2 gRB 3 gRC U (V) 32 80 100 63 40 25 50 a= 130 A2=0.6 B1= 1.25 B2= 0.6 Cf3= 0.8 10 3 10 2 7% tolerance for mean pre-arcing current 10 1 10 -1 10 -2 10 -3 10 -4 10 10 2 10 3 10 4 I (A) Above: Curves indicate, for each rated current, pre-arcing time vs. R.M.S. pre-arcing current. 12/04 1000 Above: Curves indicate for various time constants L/R the peak arc voltage which may appear across fuse terminals, vs. DC working voltage Time vs. current characteristics 10 4 U (V) 1- L/R = 50 ms 2- L/R = 25 ms 3- L/R = 15 ms Max. AC voltage (50/60 Hz): 1500 V with breaking capacity of 100 kA t (s) 800 600 400 Above: Curves indicate maximum permissible value of time constant L/R as a function of DC working voltage 200 0 0 1200 1100 1000 900 800 1000 700 90 80 70 60 50 40 30 20 10 0 SCDC11