3210-PR-TF
Thin Flex Current Probe
Instruction Sheet
Introduction
The 3210-PR-TF Flex Thin Flex Current Probe (the Probe or Product) is
an ac current probe utilizing the Rogowski principle. The Probe is
designed for use with the Fluke 1750 Power Recorder and measures
current from very low frequencies up to the 50th harmonic of a 50/60 Hz
power supply. The flexible and lightweight measuring head allows quick
and easy installation in hard to reach areas and around large conductors.
Contacting Fluke
To contact Fluke, call one of the following telephone numbers:
Technical Support USA: 1-800-44-FLUKE (1-800-443-5853)
Calibration/Repair USA: 1-888-99-FLUKE (1-888-993-5853)
Canada: 1-800-36-FLUKE (1-800-363-5853)
Europe: +31 402-675-200
Japan: +81-3-3434-0181
Singapore: +65-738-5655
Anywhere in the world: +1-425-446-5500
Or, visit Fluke's website at www.fluke.com.
To register your product, visit http://register.fluke.com.
To view, print, or download the latest manual supplement, visit
http://us.fluke.com/usen/support/manuals.
3210-PR-TF English Instruction Sheet
Page 2
Symbols
The table below lists the symbols used on the Probe and/or in this
instruction sheet.
Symbol Description
Do not dispose of this product as unsorted municipal
waste. Go to Fluke’s website for recycling information.
Important Information. See manual.
Hazardous Voltage. Risk of electric shock.
Double insulation.
Do not apply to or remove from hazardous, live
conductors, without using personal protective
equipment.
Canadian Standards Association- Complies with
relevant North American Safety Standards.
Complies with the relevant European standards.
Conforms to relevant Australian standards.
CAT III
Equipment is designed to protect against transients in
equipment in fixed equipment installations, such as
distribution panels, feeders and short branch circuits,
and lighting systems in large buildings.
CAT IV
Equipment is designed to protect against transients
from the primary supply level, such as an electricity
meter or an overhead or underground utility service.
Safety Instructions
Please read this section carefully. It will familiarize you with the most
important safety instructions for handling the Probe. In this instruction
sheet, a Warning identifies conditions and actions that pose hazard(s) to
the user. A Caution identifies conditions and actions that may damage
the Probe or the test equipment.
 Warning
To prevent possible electrical shock, fire, or personal injury:
The Probe is to only be used and handled by qualified
personnel.
Always connect to display device before it is installed
around the conductor.
Use the Product only as specified, or the protection
supplied by the Product can be compromised.
High voltages and currents can be in adjacent circuits
under test.
Before each use, examine the Product. Look for cracks or
missing pieces of the clamp housing or output cable
insulation. Also look for loose or weakened components.
Carefully examine the insulation around the jaws.
Do not use if the output cable wear indicator shows
(contrasting color inner insulation).
Do not use and disable the Product if it is damaged.
3210-PR-TF English Instruction Sheet
Page 3
Comply with local and national safety codes. Use
personal protective equipment (approved rubber gloves,
face protection, and flame-resistant clothes) to prevent
shock and arc blast injury where hazardous live
conductors are exposed.
Do not work alone.
Limit operation to the specified measurement category,
voltage, or amperage ratings.
De-energize the circuit or wear personal protective
equipment in compliance with local requirements before
you apply or remove the Flexible Current Probe.
Do not touch voltages > 30 V ac rms, 42 V ac peak, or
60 V dc.
Equipment is to be used in 600 V CAT IV and 1000 V
CAT III environments.
Do not use the Product around explosive gas, vapor, or in
damp or wet environments.
Operating Instructions
1. Connect the Probe to the 1750 via the 1750 current input jack.
2. Wear protective equipment or de-energize the circuit and place
the Probe around the conductor under test. To lock the coil,
see Figure 1.
3. Re-energize the circuit.
4. Observe and take measurements as required. Positive output
indicates that the current flow is in the direction shown by the
arrow on the Probe.
5. Wear protective gloves or de-energize the circuit before
removal of the Probe.
fig1.eps
Figure 1. Locking the Coil
Maintenance
Clean the Probe periodically by wiping it with a damp cloth and detergent.
Do not use abrasive cleaners or solvents. Do not immerse the Probe in
liquids.
3210-PR-TF English Instruction Sheet
Page 4
Specifications
Electrical Characteristics
Measurement Range 20 to 1000 A (with a crest factor 3)
Frequency Range 40 Hz to 5 kHz
Accuracy (@ 25 °C) ±1 % of reading
Linearity (10 % to 100 % of range) ±0.2 % of reading
Temperature Coefficient ±0.05 % of reading per °C
Position Sensitivity (with cable >25
mm from the coupling)
±2 % of reading
External Field (with cable >200 mm
from the head)
±1 % of reading
Working Voltage (see Safety
Standards)
1000 V ac rms or dc
General Characteristics
Probe and Cable Material Alcryn 2070NC, reinforced insulation,
UL94 V0, Color: RED
Probe Cable Length 24 in. (610 mm)
Probe Cable Diameter 0.3 in. (8 mm)
Transducer Bend Radius (min) 1.5 in. (38.1 mm)
Output Cable 2 core screened, double insulated, 3
meters long
Output Connector LEMO 6 pin male connector
Operating Temperature Range -4 to +158 °F (-20 to +70 °C) (the
temperature of the conductor under test
shall not exceed 176 °F /80 °C)
Storage Temperature Range -40 to 176 °F (-40 to +80 °C)
Operating Humidity 15 % to 85 % (non condensing)
Altitude max 6562 ft. (2000 m)
Degree of ingress protection IP40 (IEC 60529)
Safety Standards
EN/IEC 61010-1:2001
EN/IEC 61010-031:2002+A1:2008
EN/IEC 61010-2-032:2002
Pollution Degree 2
Use of the Probe on uninsulated conductors is limited to 1000 V under CAT III
installations and 600 V under CAT IV installations ac rms or dc and frequencies
below 1 kHz.
Note that the safety rating for the output to ground is limited to 30 V ac rms or dc by
the connector specified.
LIMITED WARRANTY AND LIMITATION OF LIABILITY
This Fluke product will be free from defects in material and workmanship for one
year from the date of purchase. This warranty does not cover fuses, disposable
batteries, or damage from accident, neglect, misuse, alteration, contamination, or
abnormal conditions of operation or handling. Resellers are not authorized to extend
any other warranty on Fluke’s behalf. To obtain service during the warranty period,
contact your nearest Fluke authorized service center to obtain return authorization
information, then send the product to that Service Center with a description of the
problem.
THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER WARRANTIES, SUCH
AS FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSED OR IMPLIED.
FLUKE IS NOT LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR
CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM ANY CAUSE OR
THEORY. Since some states or countries do not allow the exclusion or limitation of
an implied warranty or of incidental or consequential damages, this limitation of
liability may not apply to you.
Fluke Corporation
P.O. Box 9090
Everett, WA 98206-9090
U.S.A.
Fluke Europe B.V.
P.O. Box 1186
5602 BD Eindhoven
The Netherlands
11/99